Kabelarea för 50 Ampere vid 50 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 50 A över 50 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 6.69V (2.91%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.04V (2.19%)
Voltage at Load223.3 VLine Loss: 334.4 W
Max Power & Breaker11.5 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A71.33 V (31.01%)158.7 V117.67 V (51.16%)3566.7 WDrop High
2.5 mm²24 A18 A42.8 V (18.61%)187.2 V70.6 V (30.7%)2140.0 WDrop High
4 mm²32 A25 A26.75 V (11.63%)203.2 V44.12 V (19.18%)1337.5 WDrop High
6 mm²41 A32 A17.83 V (7.75%)212.2 V29.42 V (12.79%)891.7 WDrop High
10 mm²57 A44 A10.7 V (4.65%)219.3 V17.65 V (7.67%)535.0 W~ ≤5%
16 mm²76 A59 A6.69 V (2.91%)223.3 V11.03 V (4.8%)334.4 W✓ OK (≤3%)
25 mm²101 A78 A4.28 V (1.86%)225.7 V7.06 V (3.07%)214.0 W✓ OK (≤3%)
35 mm²125 A97 A3.06 V (1.33%)226.9 V5.04 V (2.19%)152.9 W✓ OK (≤3%)
50 mm²151 A118 A2.14 V (0.93%)227.9 V3.53 V (1.53%)107.0 W✓ OK (≤3%)
70 mm²192 A150 A1.53 V (0.66%)228.5 V2.52 V (1.1%)76.4 W✓ OK (≤3%)
95 mm²232 A181 A1.13 V (0.49%)228.9 V1.86 V (0.81%)56.3 W✓ OK (≤3%)
120 mm²269 A210 A0.89 V (0.39%)229.1 V1.47 V (0.64%)44.6 W✓ OK (≤3%)
150 mm²309 A241 A0.71 V (0.31%)229.3 V1.18 V (0.51%)35.7 W✓ OK (≤3%)
185 mm²353 A275 A0.58 V (0.25%)229.4 V0.95 V (0.41%)28.9 W✓ OK (≤3%)
240 mm²415 A324 A0.45 V (0.19%)229.6 V0.74 V (0.32%)22.3 W✓ OK (≤3%)
300 mm²477 A372 A0.36 V (0.16%)229.6 V0.59 V (0.26%)17.8 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (0.12%)229.7 V0.44 V (0.19%)13.4 W✓ OK (≤3%)

FAQ — Kabelarea för 50 Ampere vid 50 Meter (230V)

Vilken kabelarea krävs för 50A vid 50 meter (230V)?

För 50 Ampere över 50 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.69V / 2.91%).

Hur stor effekt motsvarar 50A vid 230V?

Det motsvarar 11.5 kW med en rekommenderad säkring på 50A.