Kabelarea för 63 Ampere vid 10 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 10 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 1.69V (0.73%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.78V (0.77%)
Voltage at Load228.3 VLine Loss: 106.2 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.98 V (7.82%)212.0 V29.65 V (12.89%)1132.5 WDrop High
2.5 mm²24 A18 A10.79 V (4.69%)219.2 V17.79 V (7.74%)679.5 WDrop High
4 mm²32 A25 A6.74 V (2.93%)223.3 V11.12 V (4.83%)424.7 WDrop High
6 mm²41 A32 A4.49 V (1.95%)225.5 V7.41 V (3.22%)283.1 WDrop High
10 mm²57 A44 A2.7 V (1.17%)227.3 V4.45 V (1.93%)169.9 WDrop High
16 mm²76 A59 A1.69 V (0.73%)228.3 V2.78 V (1.21%)106.2 W✓ OK (≤3%)
25 mm²101 A78 A1.08 V (0.47%)228.9 V1.78 V (0.77%)67.9 W✓ OK (≤3%)
35 mm²125 A97 A0.77 V (0.33%)229.2 V1.27 V (0.55%)48.5 W✓ OK (≤3%)
50 mm²151 A118 A0.54 V (0.23%)229.5 V0.89 V (0.39%)34.0 W✓ OK (≤3%)
70 mm²192 A150 A0.39 V (0.17%)229.6 V0.64 V (0.28%)24.3 W✓ OK (≤3%)
95 mm²232 A181 A0.28 V (0.12%)229.7 V0.47 V (0.2%)17.9 W✓ OK (≤3%)
120 mm²269 A210 A0.22 V (0.1%)229.8 V0.37 V (0.16%)14.2 W✓ OK (≤3%)
150 mm²309 A241 A0.18 V (0.08%)229.8 V0.3 V (0.13%)11.3 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.06%)229.9 V0.24 V (0.1%)9.2 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.05%)229.9 V0.19 V (0.08%)7.1 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.04%)229.9 V0.15 V (0.06%)5.7 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.03%)229.9 V0.11 V (0.05%)4.2 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 10 Meter (230V)

Vilken kabelarea krävs för 63A vid 10 meter (230V)?

För 63 Ampere över 10 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (1.69V / 0.73%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.