Kabelarea för 500 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 500 A över 150 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 6.95V (1.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.46V (2.87%)
Voltage at Load393.1 VLine Loss: 6018.7 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1853.29 V (463.32%)0.0 V3057.07 V (764.27%)1605000.0 WDrop High
2.5 mm²24 A18 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)963000.0 WDrop High
4 mm²32 A25 A694.99 V (173.75%)0.0 V1146.4 V (286.6%)601875.0 WDrop High
6 mm²41 A32 A463.32 V (115.83%)0.0 V764.27 V (191.07%)401250.0 WDrop High
10 mm²57 A44 A277.99 V (69.5%)122.0 V458.56 V (114.64%)240750.0 WDrop High
16 mm²76 A59 A173.75 V (43.44%)226.3 V286.6 V (71.65%)150468.8 WDrop High
25 mm²101 A78 A111.2 V (27.8%)288.8 V183.42 V (45.86%)96300.0 WDrop High
35 mm²125 A97 A79.43 V (19.86%)320.6 V131.02 V (32.75%)68785.7 WDrop High
50 mm²151 A118 A55.6 V (13.9%)344.4 V91.71 V (22.93%)48150.0 WDrop High
70 mm²192 A150 A39.71 V (9.93%)360.3 V65.51 V (16.38%)34392.9 WDrop High
95 mm²232 A181 A29.26 V (7.32%)370.7 V48.27 V (12.07%)25342.1 WDrop High
120 mm²269 A210 A23.17 V (5.79%)376.8 V38.21 V (9.55%)20062.5 WDrop High
150 mm²309 A241 A18.53 V (4.63%)381.5 V30.57 V (7.64%)16050.0 WDrop High
185 mm²353 A275 A15.03 V (3.76%)385.0 V24.79 V (6.2%)13013.5 WDrop High
240 mm²415 A324 A11.58 V (2.9%)388.4 V19.11 V (4.78%)10031.2 WDrop High
300 mm²477 A372 A9.27 V (2.32%)390.7 V15.29 V (3.82%)8025.0 WDrop High
400 mm²570 A445 A6.95 V (1.74%)393.1 V11.46 V (2.87%)6018.7 W✓ OK (≤3%)

FAQ — Kabelarea för 500 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 500A vid 150 meter (400V)?

För 500 Ampere över 150 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.95V / 1.74%).

Hur stor effekt motsvarar 500A vid 400V?

Det motsvarar 346.41 kW med en rekommenderad säkring på 500A.