Kabelarea för 32 Ampere vid 150 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 150 m vid 400V.
Copper Cable (≤3% Drop)16 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 11.74V (2.93%)
Voltage at Load388.9 VLine Loss: 616.3 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 118.61 V (29.65%) | 281.4 V | 195.65 V (48.91%) | 6574.1 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 71.17 V (17.79%) | 328.8 V | 117.39 V (29.35%) | 3944.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 44.48 V (11.12%) | 355.5 V | 73.37 V (18.34%) | 2465.3 W | Drop High |
| 6 mm² | 41 A | 32 A | 29.65 V (7.41%) | 370.3 V | 48.91 V (12.23%) | 1643.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 17.79 V (4.45%) | 382.2 V | 29.35 V (7.34%) | 986.1 W | ~ ≤5% |
| 16 mm² | 76 A | 59 A | 11.12 V (2.78%) | 388.9 V | 18.34 V (4.59%) | 616.3 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 7.12 V (1.78%) | 392.9 V | 11.74 V (2.93%) | 394.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 5.08 V (1.27%) | 394.9 V | 8.39 V (2.1%) | 281.7 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.56 V (0.89%) | 396.4 V | 5.87 V (1.47%) | 197.2 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.54 V (0.64%) | 397.5 V | 4.19 V (1.05%) | 140.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.87 V (0.47%) | 398.1 V | 3.09 V (0.77%) | 103.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.48 V (0.37%) | 398.5 V | 2.45 V (0.61%) | 82.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.19 V (0.3%) | 398.8 V | 1.96 V (0.49%) | 65.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.96 V (0.24%) | 399.0 V | 1.59 V (0.4%) | 53.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.74 V (0.19%) | 399.3 V | 1.22 V (0.31%) | 41.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.59 V (0.15%) | 399.4 V | 0.98 V (0.24%) | 32.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.44 V (0.11%) | 399.6 V | 0.73 V (0.18%) | 24.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 32 Ampere vid 150 Meter (400V)
Vilken kabelarea krävs för 32A vid 150 meter (400V)?
För 32 Ampere över 150 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).
Hur stor effekt motsvarar 32A vid 400V?
Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 15m (400V)32A · 20m (400V)32A · 25m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 150m (400V)16A · 150m (400V)20A · 150m (400V)25A · 150m (400V)40A · 150m (400V)50A · 150m (400V)63A · 150m (400V)80A · 150m (400V)100A · 150m (400V)125A · 150m (400V)160A · 150m (400V)200A · 150m (400V)