Kabelarea för 63 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 150 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 10.01V (2.5%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.56V (2.89%)
Voltage at Load390.0 VLine Loss: 1092.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A233.52 V (58.38%)166.5 V385.19 V (96.3%)25481.0 WDrop High
2.5 mm²24 A18 A140.11 V (35.03%)259.9 V231.11 V (57.78%)15288.6 WDrop High
4 mm²32 A25 A87.57 V (21.89%)312.4 V144.45 V (36.11%)9555.4 WDrop High
6 mm²41 A32 A58.38 V (14.59%)341.6 V96.3 V (24.07%)6370.2 WDrop High
10 mm²57 A44 A35.03 V (8.76%)365.0 V57.78 V (14.44%)3822.1 WDrop High
16 mm²76 A59 A21.89 V (5.47%)378.1 V36.11 V (9.03%)2388.8 WDrop High
25 mm²101 A78 A14.01 V (3.5%)386.0 V23.11 V (5.78%)1528.9 W~ ≤5%
35 mm²125 A97 A10.01 V (2.5%)390.0 V16.51 V (4.13%)1092.0 W✓ OK (≤3%)
50 mm²151 A118 A7.01 V (1.75%)393.0 V11.56 V (2.89%)764.4 W✓ OK (≤3%)
70 mm²192 A150 A5.0 V (1.25%)395.0 V8.25 V (2.06%)546.0 W✓ OK (≤3%)
95 mm²232 A181 A3.69 V (0.92%)396.3 V6.08 V (1.52%)402.3 W✓ OK (≤3%)
120 mm²269 A210 A2.92 V (0.73%)397.1 V4.81 V (1.2%)318.5 W✓ OK (≤3%)
150 mm²309 A241 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 W✓ OK (≤3%)
185 mm²353 A275 A1.89 V (0.47%)398.1 V3.12 V (0.78%)206.6 W✓ OK (≤3%)
240 mm²415 A324 A1.46 V (0.36%)398.5 V2.41 V (0.6%)159.3 W✓ OK (≤3%)
300 mm²477 A372 A1.17 V (0.29%)398.8 V1.93 V (0.48%)127.4 W✓ OK (≤3%)
400 mm²570 A445 A0.88 V (0.22%)399.1 V1.44 V (0.36%)95.6 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 63A vid 150 meter (400V)?

För 63 Ampere över 150 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (10.01V / 2.5%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.