Kabelarea för 63 Ampere vid 150 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 150 m vid 400V.
Copper Cable (≤3% Drop)35 mm²Drop: 10.01V (2.5%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.56V (2.89%)
Voltage at Load390.0 VLine Loss: 1092.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 233.52 V (58.38%) | 166.5 V | 385.19 V (96.3%) | 25481.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 140.11 V (35.03%) | 259.9 V | 231.11 V (57.78%) | 15288.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 87.57 V (21.89%) | 312.4 V | 144.45 V (36.11%) | 9555.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 58.38 V (14.59%) | 341.6 V | 96.3 V (24.07%) | 6370.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 35.03 V (8.76%) | 365.0 V | 57.78 V (14.44%) | 3822.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 21.89 V (5.47%) | 378.1 V | 36.11 V (9.03%) | 2388.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 14.01 V (3.5%) | 386.0 V | 23.11 V (5.78%) | 1528.9 W | ~ ≤5% |
| 35 mm² | 125 A | 97 A | 10.01 V (2.5%) | 390.0 V | 16.51 V (4.13%) | 1092.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 7.01 V (1.75%) | 393.0 V | 11.56 V (2.89%) | 764.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 5.0 V (1.25%) | 395.0 V | 8.25 V (2.06%) | 546.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 3.69 V (0.92%) | 396.3 V | 6.08 V (1.52%) | 402.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 2.92 V (0.73%) | 397.1 V | 4.81 V (1.2%) | 318.5 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 2.34 V (0.58%) | 397.7 V | 3.85 V (0.96%) | 254.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.89 V (0.47%) | 398.1 V | 3.12 V (0.78%) | 206.6 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.46 V (0.36%) | 398.5 V | 2.41 V (0.6%) | 159.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.17 V (0.29%) | 398.8 V | 1.93 V (0.48%) | 127.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.88 V (0.22%) | 399.1 V | 1.44 V (0.36%) | 95.6 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 63 Ampere vid 150 Meter (400V)
Vilken kabelarea krävs för 63A vid 150 meter (400V)?
För 63 Ampere över 150 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (10.01V / 2.5%).
Hur stor effekt motsvarar 63A vid 400V?
Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.
Related Lengths & Currents (400V)
63A · 5m (400V)63A · 10m (400V)63A · 15m (400V)63A · 20m (400V)63A · 25m (400V)63A · 30m (400V)63A · 35m (400V)63A · 40m (400V)63A · 45m (400V)63A · 50m (400V)63A · 60m (400V)63A · 70m (400V)10A · 150m (400V)16A · 150m (400V)20A · 150m (400V)25A · 150m (400V)32A · 150m (400V)40A · 150m (400V)50A · 150m (400V)80A · 150m (400V)100A · 150m (400V)125A · 150m (400V)160A · 150m (400V)200A · 150m (400V)