Kabelarea för 500 Ampere vid 200 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 500 A över 200 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 15.29V (3.82%)
Voltage at Load390.7 VLine Loss: 8025.0 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2471.06 V (617.76%)0.0 V4076.09 V (1019.02%)2140000.0 WDrop High
2.5 mm²24 A18 A1482.64 V (370.66%)0.0 V2445.66 V (611.41%)1284000.0 WDrop High
4 mm²32 A25 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)802500.0 WDrop High
6 mm²41 A32 A617.76 V (154.44%)0.0 V1019.02 V (254.76%)535000.0 WDrop High
10 mm²57 A44 A370.66 V (92.66%)29.3 V611.41 V (152.85%)321000.0 WDrop High
16 mm²76 A59 A231.66 V (57.92%)168.3 V382.13 V (95.53%)200625.0 WDrop High
25 mm²101 A78 A148.26 V (37.07%)251.7 V244.57 V (61.14%)128400.0 WDrop High
35 mm²125 A97 A105.9 V (26.48%)294.1 V174.69 V (43.67%)91714.3 WDrop High
50 mm²151 A118 A74.13 V (18.53%)325.9 V122.28 V (30.57%)64200.0 WDrop High
70 mm²192 A150 A52.95 V (13.24%)347.0 V87.34 V (21.84%)45857.1 WDrop High
95 mm²232 A181 A39.02 V (9.75%)361.0 V64.36 V (16.09%)33789.5 WDrop High
120 mm²269 A210 A30.89 V (7.72%)369.1 V50.95 V (12.74%)26750.0 WDrop High
150 mm²309 A241 A24.71 V (6.18%)375.3 V40.76 V (10.19%)21400.0 WDrop High
185 mm²353 A275 A20.04 V (5.01%)380.0 V33.05 V (8.26%)17351.4 WDrop High
240 mm²415 A324 A15.44 V (3.86%)384.6 V25.48 V (6.37%)13375.0 WDrop High
300 mm²477 A372 A12.36 V (3.09%)387.6 V20.38 V (5.1%)10700.0 WDrop High
400 mm²570 A445 A9.27 V (2.32%)390.7 V15.29 V (3.82%)8025.0 W✓ OK (≤3%)

FAQ — Kabelarea för 500 Ampere vid 200 Meter (400V)

Vilken kabelarea krävs för 500A vid 200 meter (400V)?

För 500 Ampere över 200 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (9.27V / 2.32%).

Hur stor effekt motsvarar 500A vid 400V?

Det motsvarar 346.41 kW med en rekommenderad säkring på 500A.