Kabelarea för 160 Ampere vid 200 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 200 m vid 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.58V (2.64%)
Voltage at Load390.1 VLine Loss: 2739.2 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (197.68%)0.0 V1304.35 V (326.09%)219136.0 WDrop High
2.5 mm²24 A18 A474.44 V (118.61%)0.0 V782.61 V (195.65%)131481.6 WDrop High
4 mm²32 A25 A296.53 V (74.13%)103.5 V489.13 V (122.28%)82176.0 WDrop High
6 mm²41 A32 A197.68 V (49.42%)202.3 V326.09 V (81.52%)54784.0 WDrop High
10 mm²57 A44 A118.61 V (29.65%)281.4 V195.65 V (48.91%)32870.4 WDrop High
16 mm²76 A59 A74.13 V (18.53%)325.9 V122.28 V (30.57%)20544.0 WDrop High
25 mm²101 A78 A47.44 V (11.86%)352.6 V78.26 V (19.57%)13148.2 WDrop High
35 mm²125 A97 A33.89 V (8.47%)366.1 V55.9 V (13.98%)9391.5 WDrop High
50 mm²151 A118 A23.72 V (5.93%)376.3 V39.13 V (9.78%)6574.1 WDrop High
70 mm²192 A150 A16.94 V (4.24%)383.1 V27.95 V (6.99%)4695.8 W~ ≤5%
95 mm²232 A181 A12.49 V (3.12%)387.5 V20.59 V (5.15%)3460.0 W~ ≤5%
120 mm²269 A210 A9.88 V (2.47%)390.1 V16.3 V (4.08%)2739.2 W✓ OK (≤3%)
150 mm²309 A241 A7.91 V (1.98%)392.1 V13.04 V (3.26%)2191.4 W✓ OK (≤3%)
185 mm²353 A275 A6.41 V (1.6%)393.6 V10.58 V (2.64%)1776.8 W✓ OK (≤3%)
240 mm²415 A324 A4.94 V (1.24%)395.1 V8.15 V (2.04%)1369.6 W✓ OK (≤3%)
300 mm²477 A372 A3.95 V (0.99%)396.0 V6.52 V (1.63%)1095.7 W✓ OK (≤3%)
400 mm²570 A445 A2.97 V (0.74%)397.0 V4.89 V (1.22%)821.8 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 200 Meter (400V)

Vilken kabelarea krävs för 160A vid 200 meter (400V)?

För 160 Ampere över 200 meter vid 400V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (9.88V / 2.47%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.