Kabelarea för 200 Ampere vid 200 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 200 A över 200 m vid 400V.
Copper Cable (≤3% Drop)150 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 10.19V (2.55%)
Voltage at Load390.1 VLine Loss: 3424.0 W
Max Power & Breaker138.56 kW200A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 200m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 988.42 V (247.11%) | 0.0 V | 1630.44 V (407.61%) | 342400.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 593.05 V (148.26%) | 0.0 V | 978.26 V (244.57%) | 205440.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 370.66 V (92.66%) | 29.3 V | 611.41 V (152.85%) | 128400.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 247.11 V (61.78%) | 152.9 V | 407.61 V (101.9%) | 85600.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 148.26 V (37.07%) | 251.7 V | 244.57 V (61.14%) | 51360.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 92.66 V (23.17%) | 307.3 V | 152.85 V (38.21%) | 32100.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 59.31 V (14.83%) | 340.7 V | 97.83 V (24.46%) | 20544.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 42.36 V (10.59%) | 357.6 V | 69.88 V (17.47%) | 14674.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 29.65 V (7.41%) | 370.3 V | 48.91 V (12.23%) | 10272.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 21.18 V (5.3%) | 378.8 V | 34.94 V (8.73%) | 7337.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 15.61 V (3.9%) | 384.4 V | 25.74 V (6.44%) | 5406.3 W | ~ ≤5% |
| 120 mm² | 269 A | 210 A | 12.36 V (3.09%) | 387.6 V | 20.38 V (5.1%) | 4280.0 W | ~ ≤5% |
| 150 mm² | 309 A | 241 A | 9.88 V (2.47%) | 390.1 V | 16.3 V (4.08%) | 3424.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 8.01 V (2.0%) | 392.0 V | 13.22 V (3.3%) | 2776.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 6.18 V (1.54%) | 393.8 V | 10.19 V (2.55%) | 2140.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 4.94 V (1.24%) | 395.1 V | 8.15 V (2.04%) | 1712.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 3.71 V (0.93%) | 396.3 V | 6.11 V (1.53%) | 1284.0 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 200 Ampere vid 200 Meter (400V)
Vilken kabelarea krävs för 200A vid 200 meter (400V)?
För 200 Ampere över 200 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (9.88V / 2.47%).
Hur stor effekt motsvarar 200A vid 400V?
Det motsvarar 138.56 kW med en rekommenderad säkring på 200A.
Related Lengths & Currents (400V)
200A · 5m (400V)200A · 10m (400V)200A · 15m (400V)200A · 20m (400V)200A · 25m (400V)200A · 30m (400V)200A · 35m (400V)200A · 40m (400V)200A · 45m (400V)200A · 50m (400V)200A · 60m (400V)200A · 70m (400V)10A · 200m (400V)16A · 200m (400V)20A · 200m (400V)25A · 200m (400V)32A · 200m (400V)40A · 200m (400V)50A · 200m (400V)63A · 200m (400V)80A · 200m (400V)100A · 200m (400V)125A · 200m (400V)160A · 200m (400V)