Kabelarea för 500 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 500 A över 250 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.11V (4.78%)
Voltage at Load388.4 VLine Loss: 10031.2 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3088.82 V (772.21%)0.0 V5095.12 V (1273.78%)2675000.0 WDrop High
2.5 mm²24 A18 A1853.29 V (463.32%)0.0 V3057.07 V (764.27%)1605000.0 WDrop High
4 mm²32 A25 A1158.31 V (289.58%)0.0 V1910.67 V (477.67%)1003125.0 WDrop High
6 mm²41 A32 A772.21 V (193.05%)0.0 V1273.78 V (318.44%)668750.0 WDrop High
10 mm²57 A44 A463.32 V (115.83%)0.0 V764.27 V (191.07%)401250.0 WDrop High
16 mm²76 A59 A289.58 V (72.39%)110.4 V477.67 V (119.42%)250781.2 WDrop High
25 mm²101 A78 A185.33 V (46.33%)214.7 V305.71 V (76.43%)160500.0 WDrop High
35 mm²125 A97 A132.38 V (33.09%)267.6 V218.36 V (54.59%)114642.9 WDrop High
50 mm²151 A118 A92.66 V (23.17%)307.3 V152.85 V (38.21%)80250.0 WDrop High
70 mm²192 A150 A66.19 V (16.55%)333.8 V109.18 V (27.3%)57321.4 WDrop High
95 mm²232 A181 A48.77 V (12.19%)351.2 V80.45 V (20.11%)42236.8 WDrop High
120 mm²269 A210 A38.61 V (9.65%)361.4 V63.69 V (15.92%)33437.5 WDrop High
150 mm²309 A241 A30.89 V (7.72%)369.1 V50.95 V (12.74%)26750.0 WDrop High
185 mm²353 A275 A25.04 V (6.26%)375.0 V41.31 V (10.33%)21689.2 WDrop High
240 mm²415 A324 A19.31 V (4.83%)380.7 V31.84 V (7.96%)16718.8 WDrop High
300 mm²477 A372 A15.44 V (3.86%)384.6 V25.48 V (6.37%)13375.0 WDrop High
400 mm²570 A445 A11.58 V (2.9%)388.4 V19.11 V (4.78%)10031.2 W✓ OK (≤3%)

FAQ — Kabelarea för 500 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 500A vid 250 meter (400V)?

För 500 Ampere över 250 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (11.58V / 2.9%).

Hur stor effekt motsvarar 500A vid 400V?

Det motsvarar 346.41 kW med en rekommenderad säkring på 500A.