Kabelarea för 125 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 250 m vid 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 9.65V (2.41%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.33V (2.58%)
Voltage at Load390.3 VLine Loss: 2089.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A772.21 V (193.05%)0.0 V1273.78 V (318.44%)167187.5 WDrop High
2.5 mm²24 A18 A463.32 V (115.83%)0.0 V764.27 V (191.07%)100312.5 WDrop High
4 mm²32 A25 A289.58 V (72.39%)110.4 V477.67 V (119.42%)62695.3 WDrop High
6 mm²41 A32 A193.05 V (48.26%)206.9 V318.44 V (79.61%)41796.9 WDrop High
10 mm²57 A44 A115.83 V (28.96%)284.2 V191.07 V (47.77%)25078.1 WDrop High
16 mm²76 A59 A72.39 V (18.1%)327.6 V119.42 V (29.85%)15673.8 WDrop High
25 mm²101 A78 A46.33 V (11.58%)353.7 V76.43 V (19.11%)10031.2 WDrop High
35 mm²125 A97 A33.09 V (8.27%)366.9 V54.59 V (13.65%)7165.2 WDrop High
50 mm²151 A118 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
70 mm²192 A150 A16.55 V (4.14%)383.5 V27.3 V (6.82%)3582.6 W~ ≤5%
95 mm²232 A181 A12.19 V (3.05%)387.8 V20.11 V (5.03%)2639.8 W~ ≤5%
120 mm²269 A210 A9.65 V (2.41%)390.3 V15.92 V (3.98%)2089.8 W✓ OK (≤3%)
150 mm²309 A241 A7.72 V (1.93%)392.3 V12.74 V (3.18%)1671.9 W✓ OK (≤3%)
185 mm²353 A275 A6.26 V (1.57%)393.7 V10.33 V (2.58%)1355.6 W✓ OK (≤3%)
240 mm²415 A324 A4.83 V (1.21%)395.2 V7.96 V (1.99%)1044.9 W✓ OK (≤3%)
300 mm²477 A372 A3.86 V (0.97%)396.1 V6.37 V (1.59%)835.9 W✓ OK (≤3%)
400 mm²570 A445 A2.9 V (0.72%)397.1 V4.78 V (1.19%)627.0 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 125A vid 250 meter (400V)?

För 125 Ampere över 250 meter vid 400V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (9.65V / 2.41%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.