Kabelarea för 160 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 250 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 9.88V (2.47%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 10.19V (2.55%)
Voltage at Load390.1 VLine Loss: 2739.2 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A988.42 V (247.11%)0.0 V1630.44 V (407.61%)273920.0 WDrop High
2.5 mm²24 A18 A593.05 V (148.26%)0.0 V978.26 V (244.57%)164352.0 WDrop High
4 mm²32 A25 A370.66 V (92.66%)29.3 V611.41 V (152.85%)102720.0 WDrop High
6 mm²41 A32 A247.11 V (61.78%)152.9 V407.61 V (101.9%)68480.0 WDrop High
10 mm²57 A44 A148.26 V (37.07%)251.7 V244.57 V (61.14%)41088.0 WDrop High
16 mm²76 A59 A92.66 V (23.17%)307.3 V152.85 V (38.21%)25680.0 WDrop High
25 mm²101 A78 A59.31 V (14.83%)340.7 V97.83 V (24.46%)16435.2 WDrop High
35 mm²125 A97 A42.36 V (10.59%)357.6 V69.88 V (17.47%)11739.4 WDrop High
50 mm²151 A118 A29.65 V (7.41%)370.3 V48.91 V (12.23%)8217.6 WDrop High
70 mm²192 A150 A21.18 V (5.3%)378.8 V34.94 V (8.73%)5869.7 WDrop High
95 mm²232 A181 A15.61 V (3.9%)384.4 V25.74 V (6.44%)4325.1 W~ ≤5%
120 mm²269 A210 A12.36 V (3.09%)387.6 V20.38 V (5.1%)3424.0 W~ ≤5%
150 mm²309 A241 A9.88 V (2.47%)390.1 V16.3 V (4.08%)2739.2 W✓ OK (≤3%)
185 mm²353 A275 A8.01 V (2.0%)392.0 V13.22 V (3.3%)2221.0 W✓ OK (≤3%)
240 mm²415 A324 A6.18 V (1.54%)393.8 V10.19 V (2.55%)1712.0 W✓ OK (≤3%)
300 mm²477 A372 A4.94 V (1.24%)395.1 V8.15 V (2.04%)1369.6 W✓ OK (≤3%)
400 mm²570 A445 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1027.2 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 160A vid 250 meter (400V)?

För 160 Ampere över 250 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (9.88V / 2.47%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.