Kabelarea för 60 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 45 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 6.25V (1.56%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 6.6V (1.65%)
Voltage at Load393.7 VLine Loss: 650.0 W
Max Power & Breaker41.57 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A66.72 V (16.68%)333.3 V110.05 V (27.51%)6933.6 WDrop High
2.5 mm²24 A18 A40.03 V (10.01%)360.0 V66.03 V (16.51%)4160.2 WDrop High
4 mm²32 A25 A25.02 V (6.25%)375.0 V41.27 V (10.32%)2600.1 WDrop High
6 mm²41 A32 A16.68 V (4.17%)383.3 V27.51 V (6.88%)1733.4 WDrop High
10 mm²57 A44 A10.01 V (2.5%)390.0 V16.51 V (4.13%)1040.0 WDrop High
16 mm²76 A59 A6.25 V (1.56%)393.7 V10.32 V (2.58%)650.0 W✓ OK (≤3%)
25 mm²101 A78 A4.0 V (1.0%)396.0 V6.6 V (1.65%)416.0 W✓ OK (≤3%)
35 mm²125 A97 A2.86 V (0.71%)397.1 V4.72 V (1.18%)297.2 W✓ OK (≤3%)
50 mm²151 A118 A2.0 V (0.5%)398.0 V3.3 V (0.83%)208.0 W✓ OK (≤3%)
70 mm²192 A150 A1.43 V (0.36%)398.6 V2.36 V (0.59%)148.6 W✓ OK (≤3%)
95 mm²232 A181 A1.05 V (0.26%)398.9 V1.74 V (0.43%)109.5 W✓ OK (≤3%)
120 mm²269 A210 A0.83 V (0.21%)399.2 V1.38 V (0.34%)86.7 W✓ OK (≤3%)
150 mm²309 A241 A0.67 V (0.17%)399.3 V1.1 V (0.28%)69.3 W✓ OK (≤3%)
185 mm²353 A275 A0.54 V (0.14%)399.5 V0.89 V (0.22%)56.2 W✓ OK (≤3%)
240 mm²415 A324 A0.42 V (0.1%)399.6 V0.69 V (0.17%)43.3 W✓ OK (≤3%)
300 mm²477 A372 A0.33 V (0.08%)399.7 V0.55 V (0.14%)34.7 W✓ OK (≤3%)
400 mm²570 A445 A0.25 V (0.06%)399.7 V0.41 V (0.1%)26.0 W✓ OK (≤3%)

FAQ — Kabelarea för 60 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 60A vid 45 meter (400V)?

För 60 Ampere över 45 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.25V / 1.56%).

Hur stor effekt motsvarar 60A vid 400V?

Det motsvarar 41.57 kW med en rekommenderad säkring på 60A.