Kabelarea för 60 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 10 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 1.39V (0.35%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.47V (0.37%)
Voltage at Load398.6 VLine Loss: 144.4 W
Max Power & Breaker41.57 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.83 V (3.71%)385.2 V24.46 V (6.11%)1540.8 WDrop High
2.5 mm²24 A18 A8.9 V (2.22%)391.1 V14.67 V (3.67%)924.5 WDrop High
4 mm²32 A25 A5.56 V (1.39%)394.4 V9.17 V (2.29%)577.8 WDrop High
6 mm²41 A32 A3.71 V (0.93%)396.3 V6.11 V (1.53%)385.2 WDrop High
10 mm²57 A44 A2.22 V (0.56%)397.8 V3.67 V (0.92%)231.1 WDrop High
16 mm²76 A59 A1.39 V (0.35%)398.6 V2.29 V (0.57%)144.4 W✓ OK (≤3%)
25 mm²101 A78 A0.89 V (0.22%)399.1 V1.47 V (0.37%)92.4 W✓ OK (≤3%)
35 mm²125 A97 A0.64 V (0.16%)399.4 V1.05 V (0.26%)66.0 W✓ OK (≤3%)
50 mm²151 A118 A0.44 V (0.11%)399.6 V0.73 V (0.18%)46.2 W✓ OK (≤3%)
70 mm²192 A150 A0.32 V (0.08%)399.7 V0.52 V (0.13%)33.0 W✓ OK (≤3%)
95 mm²232 A181 A0.23 V (0.06%)399.8 V0.39 V (0.1%)24.3 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.05%)399.8 V0.31 V (0.08%)19.3 W✓ OK (≤3%)
150 mm²309 A241 A0.15 V (0.04%)399.9 V0.24 V (0.06%)15.4 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.03%)399.9 V0.2 V (0.05%)12.5 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.02%)399.9 V0.15 V (0.04%)9.6 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.02%)399.9 V0.12 V (0.03%)7.7 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)399.9 V0.09 V (0.02%)5.8 W✓ OK (≤3%)

FAQ — Kabelarea för 60 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 60A vid 10 meter (400V)?

För 60 Ampere över 10 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (1.39V / 0.35%).

Hur stor effekt motsvarar 60A vid 400V?

Det motsvarar 41.57 kW med en rekommenderad säkring på 60A.