⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 600 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 150 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.17V (1.04%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 13.76V (3.44%)
Voltage at Load395.8 VLine Loss: 4333.5 W
Max Power & Breaker415.69 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)2311200.0 WDrop High
2.5 mm²24 A18 A1334.37 V (333.59%)0.0 V2201.09 V (550.27%)1386720.0 WDrop High
4 mm²32 A25 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)866700.0 WDrop High
6 mm²41 A32 A555.99 V (139.0%)0.0 V917.12 V (229.28%)577800.0 WDrop High
10 mm²57 A44 A333.59 V (83.4%)66.4 V550.27 V (137.57%)346680.0 WDrop High
16 mm²76 A59 A208.5 V (52.12%)191.5 V343.92 V (85.98%)216675.0 WDrop High
25 mm²101 A78 A133.44 V (33.36%)266.6 V220.11 V (55.03%)138672.0 WDrop High
35 mm²125 A97 A95.31 V (23.83%)304.7 V157.22 V (39.31%)99051.4 WDrop High
50 mm²151 A118 A66.72 V (16.68%)333.3 V110.05 V (27.51%)69336.0 WDrop High
70 mm²192 A150 A47.66 V (11.91%)352.3 V78.61 V (19.65%)49525.7 WDrop High
95 mm²232 A181 A35.12 V (8.78%)364.9 V57.92 V (14.48%)36492.6 WDrop High
120 mm²269 A210 A27.8 V (6.95%)372.2 V45.86 V (11.46%)28890.0 WDrop High
150 mm²309 A241 A22.24 V (5.56%)377.8 V36.68 V (9.17%)23112.0 WDrop High
185 mm²353 A275 A18.03 V (4.51%)382.0 V29.74 V (7.44%)18739.5 WDrop High
240 mm²415 A324 A13.9 V (3.47%)386.1 V22.93 V (5.73%)14445.0 WDrop High
300 mm²477 A372 A11.12 V (2.78%)388.9 V18.34 V (4.59%)11556.0 WDrop High
400 mm²570 A445 A8.34 V (2.08%)391.7 V13.76 V (3.44%)8667.0 WDrop High

FAQ — Kabelarea för 600 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 600A vid 150 meter (400V)?

För 600 Ampere över 150 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.17V / 1.04%).

Hur stor effekt motsvarar 600A vid 400V?

Det motsvarar 415.69 kW med en rekommenderad säkring på 600A.