Kabelarea för 600 Ampere vid 350 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 350 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 32.1V (8.02%)
Voltage at Load390.3 VLine Loss: 10111.5 W
Max Power & Breaker415.69 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5189.22 V (1297.31%)0.0 V8559.8 V (2139.95%)5392800.0 WDrop High
2.5 mm²24 A18 A3113.53 V (778.38%)0.0 V5135.88 V (1283.97%)3235680.0 WDrop High
4 mm²32 A25 A1945.96 V (486.49%)0.0 V3209.92 V (802.48%)2022300.0 WDrop High
6 mm²41 A32 A1297.31 V (324.33%)0.0 V2139.95 V (534.99%)1348200.0 WDrop High
10 mm²57 A44 A778.38 V (194.6%)0.0 V1283.97 V (320.99%)808920.0 WDrop High
16 mm²76 A59 A486.49 V (121.62%)0.0 V802.48 V (200.62%)505575.0 WDrop High
25 mm²101 A78 A311.35 V (77.84%)88.6 V513.59 V (128.4%)323568.0 WDrop High
35 mm²125 A97 A222.4 V (55.6%)177.6 V366.85 V (91.71%)231120.0 WDrop High
50 mm²151 A118 A155.68 V (38.92%)244.3 V256.79 V (64.2%)161784.0 WDrop High
70 mm²192 A150 A111.2 V (27.8%)288.8 V183.42 V (45.86%)115560.0 WDrop High
95 mm²232 A181 A81.94 V (20.48%)318.1 V135.15 V (33.79%)85149.5 WDrop High
120 mm²269 A210 A64.87 V (16.22%)335.1 V107.0 V (26.75%)67410.0 WDrop High
150 mm²309 A241 A51.89 V (12.97%)348.1 V85.6 V (21.4%)53928.0 WDrop High
185 mm²353 A275 A42.07 V (10.52%)357.9 V69.4 V (17.35%)43725.4 WDrop High
240 mm²415 A324 A32.43 V (8.11%)367.6 V53.5 V (13.37%)33705.0 WDrop High
300 mm²477 A372 A25.95 V (6.49%)374.1 V42.8 V (10.7%)26964.0 WDrop High
400 mm²570 A445 A19.46 V (4.86%)380.5 V32.1 V (8.02%)20223.0 WDrop High

FAQ — Kabelarea för 600 Ampere vid 350 Meter (400V)

Vilken kabelarea krävs för 600A vid 350 meter (400V)?

För 600 Ampere över 350 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (9.73V / 2.43%).

Hur stor effekt motsvarar 600A vid 400V?

Det motsvarar 415.69 kW med en rekommenderad säkring på 600A.