⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 63 Ampere vid 350 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 350 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 11.68V (2.92%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 11.23V (2.81%)
Voltage at Load388.3 VLine Loss: 1274.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A544.87 V (136.22%)0.0 V898.78 V (224.69%)59455.6 WDrop High
2.5 mm²24 A18 A326.92 V (81.73%)73.1 V539.27 V (134.82%)35673.4 WDrop High
4 mm²32 A25 A204.33 V (51.08%)195.7 V337.04 V (84.26%)22295.9 WDrop High
6 mm²41 A32 A136.22 V (34.05%)263.8 V224.69 V (56.17%)14863.9 WDrop High
10 mm²57 A44 A81.73 V (20.43%)318.3 V134.82 V (33.7%)8918.3 WDrop High
16 mm²76 A59 A51.08 V (12.77%)348.9 V84.26 V (21.07%)5574.0 WDrop High
25 mm²101 A78 A32.69 V (8.17%)367.3 V53.93 V (13.48%)3567.3 WDrop High
35 mm²125 A97 A23.35 V (5.84%)376.6 V38.52 V (9.63%)2548.1 WDrop High
50 mm²151 A118 A16.35 V (4.09%)383.7 V26.96 V (6.74%)1783.7 W~ ≤5%
70 mm²192 A150 A11.68 V (2.92%)388.3 V19.26 V (4.81%)1274.0 W✓ OK (≤3%)
95 mm²232 A181 A8.6 V (2.15%)391.4 V14.19 V (3.55%)938.8 W✓ OK (≤3%)
120 mm²269 A210 A6.81 V (1.7%)393.2 V11.23 V (2.81%)743.2 W✓ OK (≤3%)
150 mm²309 A241 A5.45 V (1.36%)394.6 V8.99 V (2.25%)594.6 W✓ OK (≤3%)
185 mm²353 A275 A4.42 V (1.1%)395.6 V7.29 V (1.82%)482.1 W✓ OK (≤3%)
240 mm²415 A324 A3.41 V (0.85%)396.6 V5.62 V (1.4%)371.6 W✓ OK (≤3%)
300 mm²477 A372 A2.72 V (0.68%)397.3 V4.49 V (1.12%)297.3 W✓ OK (≤3%)
400 mm²570 A445 A2.04 V (0.51%)398.0 V3.37 V (0.84%)223.0 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 350 Meter (400V)

Vilken kabelarea krävs för 63A vid 350 meter (400V)?

För 63 Ampere över 350 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (11.68V / 2.92%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.