Kabelarea för 160 Ampere vid 350 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 350 m vid 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 11.22V (2.8%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 11.41V (2.85%)
Voltage at Load388.8 VLine Loss: 3109.4 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1383.79 V (345.95%)0.0 V2282.61 V (570.65%)383488.0 WDrop High
2.5 mm²24 A18 A830.28 V (207.57%)0.0 V1369.57 V (342.39%)230092.8 WDrop High
4 mm²32 A25 A518.92 V (129.73%)0.0 V855.98 V (213.99%)143808.0 WDrop High
6 mm²41 A32 A345.95 V (86.49%)54.1 V570.65 V (142.66%)95872.0 WDrop High
10 mm²57 A44 A207.57 V (51.89%)192.4 V342.39 V (85.6%)57523.2 WDrop High
16 mm²76 A59 A129.73 V (32.43%)270.3 V213.99 V (53.5%)35952.0 WDrop High
25 mm²101 A78 A83.03 V (20.76%)317.0 V136.96 V (34.24%)23009.3 WDrop High
35 mm²125 A97 A59.31 V (14.83%)340.7 V97.83 V (24.46%)16435.2 WDrop High
50 mm²151 A118 A41.51 V (10.38%)358.5 V68.48 V (17.12%)11504.6 WDrop High
70 mm²192 A150 A29.65 V (7.41%)370.3 V48.91 V (12.23%)8217.6 WDrop High
95 mm²232 A181 A21.85 V (5.46%)378.2 V36.04 V (9.01%)6055.1 WDrop High
120 mm²269 A210 A17.3 V (4.32%)382.7 V28.53 V (7.13%)4793.6 W~ ≤5%
150 mm²309 A241 A13.84 V (3.46%)386.2 V22.83 V (5.71%)3834.9 W~ ≤5%
185 mm²353 A275 A11.22 V (2.8%)388.8 V18.51 V (4.63%)3109.4 W✓ OK (≤3%)
240 mm²415 A324 A8.65 V (2.16%)391.4 V14.27 V (3.57%)2396.8 W✓ OK (≤3%)
300 mm²477 A372 A6.92 V (1.73%)393.1 V11.41 V (2.85%)1917.4 W✓ OK (≤3%)
400 mm²570 A445 A5.19 V (1.3%)394.8 V8.56 V (2.14%)1438.1 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 350 Meter (400V)

Vilken kabelarea krävs för 160A vid 350 meter (400V)?

För 160 Ampere över 350 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (11.22V / 2.8%).

Hur stor effekt motsvarar 160A vid 400V?

Det motsvarar 110.85 kW med en rekommenderad säkring på 160A.