Kabelarea för 600 Ampere vid 600 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 600 A över 600 m vid 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 55.03V (13.76%)
Voltage at Load388.9 VLine Loss: 11556.0 W
Max Power & Breaker415.69 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8895.81 V (2223.95%)0.0 V14673.93 V (3668.48%)9244800.0 WDrop High
2.5 mm²24 A18 A5337.49 V (1334.37%)0.0 V8804.36 V (2201.09%)5546880.0 WDrop High
4 mm²32 A25 A3335.93 V (833.98%)0.0 V5502.73 V (1375.68%)3466800.0 WDrop High
6 mm²41 A32 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)2311200.0 WDrop High
10 mm²57 A44 A1334.37 V (333.59%)0.0 V2201.09 V (550.27%)1386720.0 WDrop High
16 mm²76 A59 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)866700.0 WDrop High
25 mm²101 A78 A533.75 V (133.44%)0.0 V880.44 V (220.11%)554688.0 WDrop High
35 mm²125 A97 A381.25 V (95.31%)18.8 V628.88 V (157.22%)396205.7 WDrop High
50 mm²151 A118 A266.87 V (66.72%)133.1 V440.22 V (110.05%)277344.0 WDrop High
70 mm²192 A150 A190.62 V (47.66%)209.4 V314.44 V (78.61%)198102.9 WDrop High
95 mm²232 A181 A140.46 V (35.12%)259.5 V231.69 V (57.92%)145970.5 WDrop High
120 mm²269 A210 A111.2 V (27.8%)288.8 V183.42 V (45.86%)115560.0 WDrop High
150 mm²309 A241 A88.96 V (22.24%)311.0 V146.74 V (36.68%)92448.0 WDrop High
185 mm²353 A275 A72.13 V (18.03%)327.9 V118.98 V (29.74%)74957.8 WDrop High
240 mm²415 A324 A55.6 V (13.9%)344.4 V91.71 V (22.93%)57780.0 WDrop High
300 mm²477 A372 A44.48 V (11.12%)355.5 V73.37 V (18.34%)46224.0 WDrop High
400 mm²570 A445 A33.36 V (8.34%)366.6 V55.03 V (13.76%)34668.0 WDrop High

FAQ — Kabelarea för 600 Ampere vid 600 Meter (400V)

Vilken kabelarea krävs för 600A vid 600 meter (400V)?

För 600 Ampere över 600 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).

Hur stor effekt motsvarar 600A vid 400V?

Det motsvarar 415.69 kW med en rekommenderad säkring på 600A.