Kabelarea för 32 Ampere vid 600 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 600 m vid 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 10.17V (2.54%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 9.78V (2.45%)
Voltage at Load389.8 VLine Loss: 563.5 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A474.44 V (118.61%)0.0 V782.61 V (195.65%)26296.3 WDrop High
2.5 mm²24 A18 A284.67 V (71.17%)115.3 V469.57 V (117.39%)15777.8 WDrop High
4 mm²32 A25 A177.92 V (44.48%)222.1 V293.48 V (73.37%)9861.1 WDrop High
6 mm²41 A32 A118.61 V (29.65%)281.4 V195.65 V (48.91%)6574.1 WDrop High
10 mm²57 A44 A71.17 V (17.79%)328.8 V117.39 V (29.35%)3944.4 WDrop High
16 mm²76 A59 A44.48 V (11.12%)355.5 V73.37 V (18.34%)2465.3 WDrop High
25 mm²101 A78 A28.47 V (7.12%)371.5 V46.96 V (11.74%)1577.8 WDrop High
35 mm²125 A97 A20.33 V (5.08%)379.7 V33.54 V (8.39%)1127.0 WDrop High
50 mm²151 A118 A14.23 V (3.56%)385.8 V23.48 V (5.87%)788.9 W~ ≤5%
70 mm²192 A150 A10.17 V (2.54%)389.8 V16.77 V (4.19%)563.5 W✓ OK (≤3%)
95 mm²232 A181 A7.49 V (1.87%)392.5 V12.36 V (3.09%)415.2 W✓ OK (≤3%)
120 mm²269 A210 A5.93 V (1.48%)394.1 V9.78 V (2.45%)328.7 W✓ OK (≤3%)
150 mm²309 A241 A4.74 V (1.19%)395.3 V7.83 V (1.96%)263.0 W✓ OK (≤3%)
185 mm²353 A275 A3.85 V (0.96%)396.2 V6.35 V (1.59%)213.2 W✓ OK (≤3%)
240 mm²415 A324 A2.97 V (0.74%)397.0 V4.89 V (1.22%)164.4 W✓ OK (≤3%)
300 mm²477 A372 A2.37 V (0.59%)397.6 V3.91 V (0.98%)131.5 W✓ OK (≤3%)
400 mm²570 A445 A1.78 V (0.44%)398.2 V2.93 V (0.73%)98.6 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 600 Meter (400V)

Vilken kabelarea krävs för 32A vid 600 meter (400V)?

För 32 Ampere över 600 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (10.17V / 2.54%).

Hur stor effekt motsvarar 32A vid 400V?

Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.