Kabelarea för 32 Ampere vid 600 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 600 m vid 400V.
Copper Cable (≤3% Drop)70 mm²Drop: 10.17V (2.54%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 9.78V (2.45%)
Voltage at Load389.8 VLine Loss: 563.5 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 474.44 V (118.61%) | 0.0 V | 782.61 V (195.65%) | 26296.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 284.67 V (71.17%) | 115.3 V | 469.57 V (117.39%) | 15777.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 177.92 V (44.48%) | 222.1 V | 293.48 V (73.37%) | 9861.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 118.61 V (29.65%) | 281.4 V | 195.65 V (48.91%) | 6574.1 W | Drop High |
| 10 mm² | 57 A | 44 A | 71.17 V (17.79%) | 328.8 V | 117.39 V (29.35%) | 3944.4 W | Drop High |
| 16 mm² | 76 A | 59 A | 44.48 V (11.12%) | 355.5 V | 73.37 V (18.34%) | 2465.3 W | Drop High |
| 25 mm² | 101 A | 78 A | 28.47 V (7.12%) | 371.5 V | 46.96 V (11.74%) | 1577.8 W | Drop High |
| 35 mm² | 125 A | 97 A | 20.33 V (5.08%) | 379.7 V | 33.54 V (8.39%) | 1127.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 14.23 V (3.56%) | 385.8 V | 23.48 V (5.87%) | 788.9 W | ~ ≤5% |
| 70 mm² | 192 A | 150 A | 10.17 V (2.54%) | 389.8 V | 16.77 V (4.19%) | 563.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 7.49 V (1.87%) | 392.5 V | 12.36 V (3.09%) | 415.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 5.93 V (1.48%) | 394.1 V | 9.78 V (2.45%) | 328.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 4.74 V (1.19%) | 395.3 V | 7.83 V (1.96%) | 263.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 3.85 V (0.96%) | 396.2 V | 6.35 V (1.59%) | 213.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 2.97 V (0.74%) | 397.0 V | 4.89 V (1.22%) | 164.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 2.37 V (0.59%) | 397.6 V | 3.91 V (0.98%) | 131.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.78 V (0.44%) | 398.2 V | 2.93 V (0.73%) | 98.6 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 32 Ampere vid 600 Meter (400V)
Vilken kabelarea krävs för 32A vid 600 meter (400V)?
För 32 Ampere över 600 meter vid 400V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (10.17V / 2.54%).
Hur stor effekt motsvarar 32A vid 400V?
Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 15m (400V)32A · 20m (400V)32A · 25m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 600m (400V)16A · 600m (400V)20A · 600m (400V)25A · 600m (400V)40A · 600m (400V)50A · 600m (400V)63A · 600m (400V)80A · 600m (400V)100A · 600m (400V)125A · 600m (400V)160A · 600m (400V)200A · 600m (400V)