Kabelarea för 63 Ampere vid 600 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 600 m vid 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 11.68V (2.92%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 9.63V (2.41%)
Voltage at Load388.3 VLine Loss: 1274.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A934.06 V (233.52%)0.0 V1540.76 V (385.19%)101923.9 WDrop High
2.5 mm²24 A18 A560.44 V (140.11%)0.0 V924.46 V (231.11%)61154.4 WDrop High
4 mm²32 A25 A350.27 V (87.57%)49.7 V577.79 V (144.45%)38221.5 WDrop High
6 mm²41 A32 A233.52 V (58.38%)166.5 V385.19 V (96.3%)25481.0 WDrop High
10 mm²57 A44 A140.11 V (35.03%)259.9 V231.11 V (57.78%)15288.6 WDrop High
16 mm²76 A59 A87.57 V (21.89%)312.4 V144.45 V (36.11%)9555.4 WDrop High
25 mm²101 A78 A56.04 V (14.01%)344.0 V92.45 V (23.11%)6115.4 WDrop High
35 mm²125 A97 A40.03 V (10.01%)360.0 V66.03 V (16.51%)4368.2 WDrop High
50 mm²151 A118 A28.02 V (7.01%)372.0 V46.22 V (11.56%)3057.7 WDrop High
70 mm²192 A150 A20.02 V (5.0%)380.0 V33.02 V (8.25%)2184.1 WDrop High
95 mm²232 A181 A14.75 V (3.69%)385.3 V24.33 V (6.08%)1609.3 W~ ≤5%
120 mm²269 A210 A11.68 V (2.92%)388.3 V19.26 V (4.81%)1274.0 W✓ OK (≤3%)
150 mm²309 A241 A9.34 V (2.34%)390.7 V15.41 V (3.85%)1019.2 W✓ OK (≤3%)
185 mm²353 A275 A7.57 V (1.89%)392.4 V12.49 V (3.12%)826.4 W✓ OK (≤3%)
240 mm²415 A324 A5.84 V (1.46%)394.2 V9.63 V (2.41%)637.0 W✓ OK (≤3%)
300 mm²477 A372 A4.67 V (1.17%)395.3 V7.7 V (1.93%)509.6 W✓ OK (≤3%)
400 mm²570 A445 A3.5 V (0.88%)396.5 V5.78 V (1.44%)382.2 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 600 Meter (400V)

Vilken kabelarea krävs för 63A vid 600 meter (400V)?

För 63 Ampere över 600 meter vid 400V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (11.68V / 2.92%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.