Kabelarea för 63 Ampere vid 600 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 600 m vid 400V.
Copper Cable (≤3% Drop)120 mm²Drop: 11.68V (2.92%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 9.63V (2.41%)
Voltage at Load388.3 VLine Loss: 1274.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 934.06 V (233.52%) | 0.0 V | 1540.76 V (385.19%) | 101923.9 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 560.44 V (140.11%) | 0.0 V | 924.46 V (231.11%) | 61154.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 350.27 V (87.57%) | 49.7 V | 577.79 V (144.45%) | 38221.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 233.52 V (58.38%) | 166.5 V | 385.19 V (96.3%) | 25481.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 140.11 V (35.03%) | 259.9 V | 231.11 V (57.78%) | 15288.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 87.57 V (21.89%) | 312.4 V | 144.45 V (36.11%) | 9555.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 56.04 V (14.01%) | 344.0 V | 92.45 V (23.11%) | 6115.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 40.03 V (10.01%) | 360.0 V | 66.03 V (16.51%) | 4368.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 28.02 V (7.01%) | 372.0 V | 46.22 V (11.56%) | 3057.7 W | Drop High |
| 70 mm² | 192 A | 150 A | 20.02 V (5.0%) | 380.0 V | 33.02 V (8.25%) | 2184.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 14.75 V (3.69%) | 385.3 V | 24.33 V (6.08%) | 1609.3 W | ~ ≤5% |
| 120 mm² | 269 A | 210 A | 11.68 V (2.92%) | 388.3 V | 19.26 V (4.81%) | 1274.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 9.34 V (2.34%) | 390.7 V | 15.41 V (3.85%) | 1019.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 7.57 V (1.89%) | 392.4 V | 12.49 V (3.12%) | 826.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 5.84 V (1.46%) | 394.2 V | 9.63 V (2.41%) | 637.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 4.67 V (1.17%) | 395.3 V | 7.7 V (1.93%) | 509.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 3.5 V (0.88%) | 396.5 V | 5.78 V (1.44%) | 382.2 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 63 Ampere vid 600 Meter (400V)
Vilken kabelarea krävs för 63A vid 600 meter (400V)?
För 63 Ampere över 600 meter vid 400V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (11.68V / 2.92%).
Hur stor effekt motsvarar 63A vid 400V?
Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.
Related Lengths & Currents (400V)
63A · 5m (400V)63A · 10m (400V)63A · 15m (400V)63A · 20m (400V)63A · 25m (400V)63A · 30m (400V)63A · 35m (400V)63A · 40m (400V)63A · 45m (400V)63A · 50m (400V)63A · 60m (400V)63A · 70m (400V)10A · 600m (400V)16A · 600m (400V)20A · 600m (400V)25A · 600m (400V)32A · 600m (400V)40A · 600m (400V)50A · 600m (400V)80A · 600m (400V)100A · 600m (400V)125A · 600m (400V)160A · 600m (400V)200A · 600m (400V)