Kabelarea för 650 Ampere vid 300 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 650 A över 300 m vid 230V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 5.21V (2.27%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 34.42V (14.96%)
Voltage at Load224.8 VLine Loss: 3390.6 W
Max Power & Breaker149.5 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 650A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5564.0 V (2419.13%)0.0 V9178.0 V (3990.43%)3616600.0 WDrop High
2.5 mm²24 A18 A3338.4 V (1451.48%)0.0 V5506.8 V (2394.26%)2169960.0 WDrop High
4 mm²32 A25 A2086.5 V (907.17%)0.0 V3441.75 V (1496.41%)1356225.0 WDrop High
6 mm²41 A32 A1391.0 V (604.78%)0.0 V2294.5 V (997.61%)904150.0 WDrop High
10 mm²57 A44 A834.6 V (362.87%)0.0 V1376.7 V (598.57%)542490.0 WDrop High
16 mm²76 A59 A521.62 V (226.79%)0.0 V860.44 V (374.1%)339056.2 WDrop High
25 mm²101 A78 A333.84 V (145.15%)0.0 V550.68 V (239.43%)216996.0 WDrop High
35 mm²125 A97 A238.46 V (103.68%)0.0 V393.34 V (171.02%)154997.1 WDrop High
50 mm²151 A118 A166.92 V (72.57%)63.1 V275.34 V (119.71%)108498.0 WDrop High
70 mm²192 A150 A119.23 V (51.84%)110.8 V196.67 V (85.51%)77498.6 WDrop High
95 mm²232 A181 A87.85 V (38.2%)142.1 V144.92 V (63.01%)57104.2 WDrop High
120 mm²269 A210 A69.55 V (30.24%)160.4 V114.72 V (49.88%)45207.5 WDrop High
150 mm²309 A241 A55.64 V (24.19%)174.4 V91.78 V (39.9%)36166.0 WDrop High
185 mm²353 A275 A45.11 V (19.61%)184.9 V74.42 V (32.35%)29323.8 WDrop High
240 mm²415 A324 A34.77 V (15.12%)195.2 V57.36 V (24.94%)22603.8 WDrop High
300 mm²477 A372 A27.82 V (12.1%)202.2 V45.89 V (19.95%)18083.0 WDrop High
400 mm²570 A445 A20.86 V (9.07%)209.1 V34.42 V (14.96%)13562.2 WDrop High

FAQ — Kabelarea för 650 Ampere vid 300 Meter (230V)

Vilken kabelarea krävs för 650A vid 300 meter (230V)?

För 650 Ampere över 300 meter vid 230V rekommenderas 4× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.21V / 2.27%).

Hur stor effekt motsvarar 650A vid 230V?

Det motsvarar 149.5 kW med en rekommenderad säkring på 700A.