Kabelarea för 63 Ampere vid 300 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 300 m vid 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 6.74V (2.93%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 5.56V (2.42%)
Voltage at Load223.3 VLine Loss: 424.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A539.28 V (234.47%)0.0 V889.56 V (386.77%)33974.6 WDrop High
2.5 mm²24 A18 A323.57 V (140.68%)0.0 V533.74 V (232.06%)20384.8 WDrop High
4 mm²32 A25 A202.23 V (87.93%)27.8 V333.58 V (145.04%)12740.5 WDrop High
6 mm²41 A32 A134.82 V (58.62%)95.2 V222.39 V (96.69%)8493.7 WDrop High
10 mm²57 A44 A80.89 V (35.17%)149.1 V133.43 V (58.01%)5096.2 WDrop High
16 mm²76 A59 A50.56 V (21.98%)179.4 V83.4 V (36.26%)3185.1 WDrop High
25 mm²101 A78 A32.36 V (14.07%)197.6 V53.37 V (23.21%)2038.5 WDrop High
35 mm²125 A97 A23.11 V (10.05%)206.9 V38.12 V (16.58%)1456.1 WDrop High
50 mm²151 A118 A16.18 V (7.03%)213.8 V26.69 V (11.6%)1019.2 WDrop High
70 mm²192 A150 A11.56 V (5.02%)218.4 V19.06 V (8.29%)728.0 WDrop High
95 mm²232 A181 A8.51 V (3.7%)221.5 V14.05 V (6.11%)536.4 W~ ≤5%
120 mm²269 A210 A6.74 V (2.93%)223.3 V11.12 V (4.83%)424.7 W✓ OK (≤3%)
150 mm²309 A241 A5.39 V (2.34%)224.6 V8.9 V (3.87%)339.7 W✓ OK (≤3%)
185 mm²353 A275 A4.37 V (1.9%)225.6 V7.21 V (3.14%)275.5 W✓ OK (≤3%)
240 mm²415 A324 A3.37 V (1.47%)226.6 V5.56 V (2.42%)212.3 W✓ OK (≤3%)
300 mm²477 A372 A2.7 V (1.17%)227.3 V4.45 V (1.93%)169.9 W✓ OK (≤3%)
400 mm²570 A445 A2.02 V (0.88%)228.0 V3.34 V (1.45%)127.4 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 300 Meter (230V)

Vilken kabelarea krävs för 63A vid 300 meter (230V)?

För 63 Ampere över 300 meter vid 230V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (6.74V / 2.93%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.