Kabelarea för 63 Ampere vid 300 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 300 m vid 230V.
Copper Cable (≤3% Drop)120 mm²Drop: 6.74V (2.93%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 5.56V (2.42%)
Voltage at Load223.3 VLine Loss: 424.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 300m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 539.28 V (234.47%) | 0.0 V | 889.56 V (386.77%) | 33974.6 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 323.57 V (140.68%) | 0.0 V | 533.74 V (232.06%) | 20384.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 202.23 V (87.93%) | 27.8 V | 333.58 V (145.04%) | 12740.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 134.82 V (58.62%) | 95.2 V | 222.39 V (96.69%) | 8493.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 80.89 V (35.17%) | 149.1 V | 133.43 V (58.01%) | 5096.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 50.56 V (21.98%) | 179.4 V | 83.4 V (36.26%) | 3185.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 32.36 V (14.07%) | 197.6 V | 53.37 V (23.21%) | 2038.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 23.11 V (10.05%) | 206.9 V | 38.12 V (16.58%) | 1456.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 16.18 V (7.03%) | 213.8 V | 26.69 V (11.6%) | 1019.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 11.56 V (5.02%) | 218.4 V | 19.06 V (8.29%) | 728.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 8.51 V (3.7%) | 221.5 V | 14.05 V (6.11%) | 536.4 W | ~ ≤5% |
| 120 mm² | 269 A | 210 A | 6.74 V (2.93%) | 223.3 V | 11.12 V (4.83%) | 424.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 5.39 V (2.34%) | 224.6 V | 8.9 V (3.87%) | 339.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 4.37 V (1.9%) | 225.6 V | 7.21 V (3.14%) | 275.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 3.37 V (1.47%) | 226.6 V | 5.56 V (2.42%) | 212.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 2.7 V (1.17%) | 227.3 V | 4.45 V (1.93%) | 169.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.02 V (0.88%) | 228.0 V | 3.34 V (1.45%) | 127.4 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 63 Ampere vid 300 Meter (230V)
Vilken kabelarea krävs för 63A vid 300 meter (230V)?
För 63 Ampere över 300 meter vid 230V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (6.74V / 2.93%).
Hur stor effekt motsvarar 63A vid 230V?
Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.
Related Lengths & Currents (230V)
63A · 5m (230V)63A · 10m (230V)63A · 15m (230V)63A · 20m (230V)63A · 25m (230V)63A · 30m (230V)63A · 35m (230V)63A · 40m (230V)63A · 45m (230V)63A · 50m (230V)63A · 60m (230V)63A · 70m (230V)10A · 300m (230V)16A · 300m (230V)20A · 300m (230V)25A · 300m (230V)32A · 300m (230V)40A · 300m (230V)50A · 300m (230V)80A · 300m (230V)100A · 300m (230V)125A · 300m (230V)160A · 300m (230V)200A · 300m (230V)