Kabelarea för 70 Ampere vid 175 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 70 A över 175 m vid 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 5.52V (2.4%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 5.77V (2.51%)
Voltage at Load224.5 VLine Loss: 386.3 W
Max Power & Breaker16.1 kW70A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 70A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A349.53 V (151.97%)0.0 V576.57 V (250.68%)24467.3 WDrop High
2.5 mm²24 A18 A209.72 V (91.18%)20.3 V345.94 V (150.41%)14680.4 WDrop High
4 mm²32 A25 A131.07 V (56.99%)98.9 V216.21 V (94.01%)9175.2 WDrop High
6 mm²41 A32 A87.38 V (37.99%)142.6 V144.14 V (62.67%)6116.8 WDrop High
10 mm²57 A44 A52.43 V (22.8%)177.6 V86.48 V (37.6%)3670.1 WDrop High
16 mm²76 A59 A32.77 V (14.25%)197.2 V54.05 V (23.5%)2293.8 WDrop High
25 mm²101 A78 A20.97 V (9.12%)209.0 V34.59 V (15.04%)1468.0 WDrop High
35 mm²125 A97 A14.98 V (6.51%)215.0 V24.71 V (10.74%)1048.6 WDrop High
50 mm²151 A118 A10.49 V (4.56%)219.5 V17.3 V (7.52%)734.0 W~ ≤5%
70 mm²192 A150 A7.49 V (3.26%)222.5 V12.35 V (5.37%)524.3 W~ ≤5%
95 mm²232 A181 A5.52 V (2.4%)224.5 V9.1 V (3.96%)386.3 W✓ OK (≤3%)
120 mm²269 A210 A4.37 V (1.9%)225.6 V7.21 V (3.13%)305.8 W✓ OK (≤3%)
150 mm²309 A241 A3.5 V (1.52%)226.5 V5.77 V (2.51%)244.7 W✓ OK (≤3%)
185 mm²353 A275 A2.83 V (1.23%)227.2 V4.67 V (2.03%)198.4 W✓ OK (≤3%)
240 mm²415 A324 A2.18 V (0.95%)227.8 V3.6 V (1.57%)152.9 W✓ OK (≤3%)
300 mm²477 A372 A1.75 V (0.76%)228.3 V2.88 V (1.25%)122.3 W✓ OK (≤3%)
400 mm²570 A445 A1.31 V (0.57%)228.7 V2.16 V (0.94%)91.8 W✓ OK (≤3%)

FAQ — Kabelarea för 70 Ampere vid 175 Meter (230V)

Vilken kabelarea krävs för 70A vid 175 meter (230V)?

För 70 Ampere över 175 meter vid 230V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (5.52V / 2.4%).

Hur stor effekt motsvarar 70A vid 230V?

Det motsvarar 16.1 kW med en rekommenderad säkring på 70A.