Kabelarea för 80 Ampere vid 15 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 80 A över 15 m vid 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 2.05V (0.89%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 2.42V (1.05%)
Voltage at Load227.9 VLine Loss: 164.4 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.24 V (14.89%)195.8 V56.48 V (24.56%)2739.2 WDrop High
2.5 mm²24 A18 A20.54 V (8.93%)209.5 V33.89 V (14.73%)1643.5 WDrop High
4 mm²32 A25 A12.84 V (5.58%)217.2 V21.18 V (9.21%)1027.2 WDrop High
6 mm²41 A32 A8.56 V (3.72%)221.4 V14.12 V (6.14%)684.8 WDrop High
10 mm²57 A44 A5.14 V (2.23%)224.9 V8.47 V (3.68%)410.9 WDrop High
16 mm²76 A59 A3.21 V (1.4%)226.8 V5.29 V (2.3%)256.8 WDrop High
25 mm²101 A78 A2.05 V (0.89%)227.9 V3.39 V (1.47%)164.4 W✓ OK (≤3%)
35 mm²125 A97 A1.47 V (0.64%)228.5 V2.42 V (1.05%)117.4 W✓ OK (≤3%)
50 mm²151 A118 A1.03 V (0.45%)229.0 V1.69 V (0.74%)82.2 W✓ OK (≤3%)
70 mm²192 A150 A0.73 V (0.32%)229.3 V1.21 V (0.53%)58.7 W✓ OK (≤3%)
95 mm²232 A181 A0.54 V (0.24%)229.5 V0.89 V (0.39%)43.3 W✓ OK (≤3%)
120 mm²269 A210 A0.43 V (0.19%)229.6 V0.71 V (0.31%)34.2 W✓ OK (≤3%)
150 mm²309 A241 A0.34 V (0.15%)229.7 V0.56 V (0.25%)27.4 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.12%)229.7 V0.46 V (0.2%)22.2 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.09%)229.8 V0.35 V (0.15%)17.1 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.07%)229.8 V0.28 V (0.12%)13.7 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.06%)229.9 V0.21 V (0.09%)10.3 W✓ OK (≤3%)

FAQ — Kabelarea för 80 Ampere vid 15 Meter (230V)

Vilken kabelarea krävs för 80A vid 15 meter (230V)?

För 80 Ampere över 15 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (2.05V / 0.89%).

Hur stor effekt motsvarar 80A vid 230V?

Det motsvarar 18.4 kW med en rekommenderad säkring på 80A.