Kabelarea för 800 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 45 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.67V (0.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.5V (1.38%)
Voltage at Load398.3 VLine Loss: 2311.2 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A889.58 V (222.4%)0.0 V1467.39 V (366.85%)1232640.0 WDrop High
2.5 mm²24 A18 A533.75 V (133.44%)0.0 V880.44 V (220.11%)739584.0 WDrop High
4 mm²32 A25 A333.59 V (83.4%)66.4 V550.27 V (137.57%)462240.0 WDrop High
6 mm²41 A32 A222.4 V (55.6%)177.6 V366.85 V (91.71%)308160.0 WDrop High
10 mm²57 A44 A133.44 V (33.36%)266.6 V220.11 V (55.03%)184896.0 WDrop High
16 mm²76 A59 A83.4 V (20.85%)316.6 V137.57 V (34.39%)115560.0 WDrop High
25 mm²101 A78 A53.37 V (13.34%)346.6 V88.04 V (22.01%)73958.4 WDrop High
35 mm²125 A97 A38.12 V (9.53%)361.9 V62.89 V (15.72%)52827.4 WDrop High
50 mm²151 A118 A26.69 V (6.67%)373.3 V44.02 V (11.01%)36979.2 WDrop High
70 mm²192 A150 A19.06 V (4.77%)380.9 V31.44 V (7.86%)26413.7 WDrop High
95 mm²232 A181 A14.05 V (3.51%)386.0 V23.17 V (5.79%)19462.7 WDrop High
120 mm²269 A210 A11.12 V (2.78%)388.9 V18.34 V (4.59%)15408.0 WDrop High
150 mm²309 A241 A8.9 V (2.22%)391.1 V14.67 V (3.67%)12326.4 WDrop High
185 mm²353 A275 A7.21 V (1.8%)392.8 V11.9 V (2.97%)9994.4 WDrop High
240 mm²415 A324 A5.56 V (1.39%)394.4 V9.17 V (2.29%)7704.0 WDrop High
300 mm²477 A372 A4.45 V (1.11%)395.6 V7.34 V (1.83%)6163.2 WDrop High
400 mm²570 A445 A3.34 V (0.83%)396.7 V5.5 V (1.38%)4622.4 WDrop High

FAQ — Kabelarea för 800 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 800A vid 45 meter (400V)?

För 800 Ampere över 45 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.67V / 0.41%).

Hur stor effekt motsvarar 800A vid 400V?

Det motsvarar 554.26 kW med en rekommenderad säkring på 800A.