Kabelarea för 800 Ampere vid 50 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 50 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.85V (0.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.11V (1.53%)
Voltage at Load398.1 VLine Loss: 2568.0 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A988.42 V (247.11%)0.0 V1630.44 V (407.61%)1369600.0 WDrop High
2.5 mm²24 A18 A593.05 V (148.26%)0.0 V978.26 V (244.57%)821760.0 WDrop High
4 mm²32 A25 A370.66 V (92.66%)29.3 V611.41 V (152.85%)513600.0 WDrop High
6 mm²41 A32 A247.11 V (61.78%)152.9 V407.61 V (101.9%)342400.0 WDrop High
10 mm²57 A44 A148.26 V (37.07%)251.7 V244.57 V (61.14%)205440.0 WDrop High
16 mm²76 A59 A92.66 V (23.17%)307.3 V152.85 V (38.21%)128400.0 WDrop High
25 mm²101 A78 A59.31 V (14.83%)340.7 V97.83 V (24.46%)82176.0 WDrop High
35 mm²125 A97 A42.36 V (10.59%)357.6 V69.88 V (17.47%)58697.1 WDrop High
50 mm²151 A118 A29.65 V (7.41%)370.3 V48.91 V (12.23%)41088.0 WDrop High
70 mm²192 A150 A21.18 V (5.3%)378.8 V34.94 V (8.73%)29348.6 WDrop High
95 mm²232 A181 A15.61 V (3.9%)384.4 V25.74 V (6.44%)21625.3 WDrop High
120 mm²269 A210 A12.36 V (3.09%)387.6 V20.38 V (5.1%)17120.0 WDrop High
150 mm²309 A241 A9.88 V (2.47%)390.1 V16.3 V (4.08%)13696.0 WDrop High
185 mm²353 A275 A8.01 V (2.0%)392.0 V13.22 V (3.3%)11104.9 WDrop High
240 mm²415 A324 A6.18 V (1.54%)393.8 V10.19 V (2.55%)8560.0 WDrop High
300 mm²477 A372 A4.94 V (1.24%)395.1 V8.15 V (2.04%)6848.0 WDrop High
400 mm²570 A445 A3.71 V (0.93%)396.3 V6.11 V (1.53%)5136.0 WDrop High

FAQ — Kabelarea för 800 Ampere vid 50 Meter (400V)

Vilken kabelarea krävs för 800A vid 50 meter (400V)?

För 800 Ampere över 50 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.85V / 0.47%).

Hur stor effekt motsvarar 800A vid 400V?

Det motsvarar 554.26 kW med en rekommenderad säkring på 800A.