⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 90 Ampere vid 25 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 25 m vid 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 3.34V (0.83%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 3.93V (0.98%)
Voltage at Load396.7 VLine Loss: 520.0 W
Max Power & Breaker62.35 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.6 V (13.9%)344.4 V91.71 V (22.93%)8667.0 WDrop High
2.5 mm²24 A18 A33.36 V (8.34%)366.6 V55.03 V (13.76%)5200.2 WDrop High
4 mm²32 A25 A20.85 V (5.21%)379.2 V34.39 V (8.6%)3250.1 WDrop High
6 mm²41 A32 A13.9 V (3.47%)386.1 V22.93 V (5.73%)2166.8 WDrop High
10 mm²57 A44 A8.34 V (2.08%)391.7 V13.76 V (3.44%)1300.0 WDrop High
16 mm²76 A59 A5.21 V (1.3%)394.8 V8.6 V (2.15%)812.5 WDrop High
25 mm²101 A78 A3.34 V (0.83%)396.7 V5.5 V (1.38%)520.0 W✓ OK (≤3%)
35 mm²125 A97 A2.38 V (0.6%)397.6 V3.93 V (0.98%)371.4 W✓ OK (≤3%)
50 mm²151 A118 A1.67 V (0.42%)398.3 V2.75 V (0.69%)260.0 W✓ OK (≤3%)
70 mm²192 A150 A1.19 V (0.3%)398.8 V1.97 V (0.49%)185.7 W✓ OK (≤3%)
95 mm²232 A181 A0.88 V (0.22%)399.1 V1.45 V (0.36%)136.8 W✓ OK (≤3%)
120 mm²269 A210 A0.69 V (0.17%)399.3 V1.15 V (0.29%)108.3 W✓ OK (≤3%)
150 mm²309 A241 A0.56 V (0.14%)399.4 V0.92 V (0.23%)86.7 W✓ OK (≤3%)
185 mm²353 A275 A0.45 V (0.11%)399.5 V0.74 V (0.19%)70.3 W✓ OK (≤3%)
240 mm²415 A324 A0.35 V (0.09%)399.7 V0.57 V (0.14%)54.2 W✓ OK (≤3%)
300 mm²477 A372 A0.28 V (0.07%)399.7 V0.46 V (0.11%)43.3 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.05%)399.8 V0.34 V (0.09%)32.5 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 25 Meter (400V)

Vilken kabelarea krävs för 90A vid 25 meter (400V)?

För 90 Ampere över 25 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (3.34V / 0.83%).

Hur stor effekt motsvarar 90A vid 400V?

Det motsvarar 62.35 kW med en rekommenderad säkring på 90A.