Kabelarea för 90 Ampere vid 70 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 70 m vid 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 9.34V (2.34%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 11.01V (2.75%)
Voltage at Load390.7 VLine Loss: 1456.1 W
Max Power & Breaker62.35 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A155.68 V (38.92%)244.3 V256.79 V (64.2%)24267.6 WDrop High
2.5 mm²24 A18 A93.41 V (23.35%)306.6 V154.08 V (38.52%)14560.6 WDrop High
4 mm²32 A25 A58.38 V (14.59%)341.6 V96.3 V (24.07%)9100.4 WDrop High
6 mm²41 A32 A38.92 V (9.73%)361.1 V64.2 V (16.05%)6066.9 WDrop High
10 mm²57 A44 A23.35 V (5.84%)376.6 V38.52 V (9.63%)3640.1 WDrop High
16 mm²76 A59 A14.59 V (3.65%)385.4 V24.07 V (6.02%)2275.1 WDrop High
25 mm²101 A78 A9.34 V (2.34%)390.7 V15.41 V (3.85%)1456.1 W✓ OK (≤3%)
35 mm²125 A97 A6.67 V (1.67%)393.3 V11.01 V (2.75%)1040.0 W✓ OK (≤3%)
50 mm²151 A118 A4.67 V (1.17%)395.3 V7.7 V (1.93%)728.0 W✓ OK (≤3%)
70 mm²192 A150 A3.34 V (0.83%)396.7 V5.5 V (1.38%)520.0 W✓ OK (≤3%)
95 mm²232 A181 A2.46 V (0.61%)397.5 V4.05 V (1.01%)383.2 W✓ OK (≤3%)
120 mm²269 A210 A1.95 V (0.49%)398.1 V3.21 V (0.8%)303.3 W✓ OK (≤3%)
150 mm²309 A241 A1.56 V (0.39%)398.4 V2.57 V (0.64%)242.7 W✓ OK (≤3%)
185 mm²353 A275 A1.26 V (0.32%)398.7 V2.08 V (0.52%)196.8 W✓ OK (≤3%)
240 mm²415 A324 A0.97 V (0.24%)399.0 V1.6 V (0.4%)151.7 W✓ OK (≤3%)
300 mm²477 A372 A0.78 V (0.19%)399.2 V1.28 V (0.32%)121.3 W✓ OK (≤3%)
400 mm²570 A445 A0.58 V (0.15%)399.4 V0.96 V (0.24%)91.0 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 70 Meter (400V)

Vilken kabelarea krävs för 90A vid 70 meter (400V)?

För 90 Ampere över 70 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (9.34V / 2.34%).

Hur stor effekt motsvarar 90A vid 400V?

Det motsvarar 62.35 kW med en rekommenderad säkring på 90A.