⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 900 Ampere vid 400 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 900 A över 400 m vid 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 55.03V (13.76%)
Voltage at Load388.9 VLine Loss: 17334.0 W
Max Power & Breaker623.54 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8895.81 V (2223.95%)0.0 V14673.93 V (3668.48%)13867200.0 WDrop High
2.5 mm²24 A18 A5337.49 V (1334.37%)0.0 V8804.36 V (2201.09%)8320320.0 WDrop High
4 mm²32 A25 A3335.93 V (833.98%)0.0 V5502.73 V (1375.68%)5200200.0 WDrop High
6 mm²41 A32 A2223.95 V (555.99%)0.0 V3668.48 V (917.12%)3466800.0 WDrop High
10 mm²57 A44 A1334.37 V (333.59%)0.0 V2201.09 V (550.27%)2080080.0 WDrop High
16 mm²76 A59 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)1300050.0 WDrop High
25 mm²101 A78 A533.75 V (133.44%)0.0 V880.44 V (220.11%)832032.0 WDrop High
35 mm²125 A97 A381.25 V (95.31%)18.8 V628.88 V (157.22%)594308.6 WDrop High
50 mm²151 A118 A266.87 V (66.72%)133.1 V440.22 V (110.05%)416016.0 WDrop High
70 mm²192 A150 A190.62 V (47.66%)209.4 V314.44 V (78.61%)297154.3 WDrop High
95 mm²232 A181 A140.46 V (35.12%)259.5 V231.69 V (57.92%)218955.8 WDrop High
120 mm²269 A210 A111.2 V (27.8%)288.8 V183.42 V (45.86%)173340.0 WDrop High
150 mm²309 A241 A88.96 V (22.24%)311.0 V146.74 V (36.68%)138672.0 WDrop High
185 mm²353 A275 A72.13 V (18.03%)327.9 V118.98 V (29.74%)112436.8 WDrop High
240 mm²415 A324 A55.6 V (13.9%)344.4 V91.71 V (22.93%)86670.0 WDrop High
300 mm²477 A372 A44.48 V (11.12%)355.5 V73.37 V (18.34%)69336.0 WDrop High
400 mm²570 A445 A33.36 V (8.34%)366.6 V55.03 V (13.76%)52002.0 WDrop High

FAQ — Kabelarea för 900 Ampere vid 400 Meter (400V)

Vilken kabelarea krävs för 900A vid 400 meter (400V)?

För 900 Ampere över 400 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).

Hur stor effekt motsvarar 900A vid 400V?

Det motsvarar 623.54 kW med en rekommenderad säkring på 1000A.