Kabelarea för 900 Ampere vid 400 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 900 A över 400 m vid 400V.
Copper Cable (≤3% Drop)3× 400 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 55.03V (13.76%)
Voltage at Load388.9 VLine Loss: 17334.0 W
Max Power & Breaker623.54 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 400m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 8895.81 V (2223.95%) | 0.0 V | 14673.93 V (3668.48%) | 13867200.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 5337.49 V (1334.37%) | 0.0 V | 8804.36 V (2201.09%) | 8320320.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 3335.93 V (833.98%) | 0.0 V | 5502.73 V (1375.68%) | 5200200.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 2223.95 V (555.99%) | 0.0 V | 3668.48 V (917.12%) | 3466800.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 1334.37 V (333.59%) | 0.0 V | 2201.09 V (550.27%) | 2080080.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 833.98 V (208.5%) | 0.0 V | 1375.68 V (343.92%) | 1300050.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 533.75 V (133.44%) | 0.0 V | 880.44 V (220.11%) | 832032.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 381.25 V (95.31%) | 18.8 V | 628.88 V (157.22%) | 594308.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 266.87 V (66.72%) | 133.1 V | 440.22 V (110.05%) | 416016.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 190.62 V (47.66%) | 209.4 V | 314.44 V (78.61%) | 297154.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 140.46 V (35.12%) | 259.5 V | 231.69 V (57.92%) | 218955.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 111.2 V (27.8%) | 288.8 V | 183.42 V (45.86%) | 173340.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 88.96 V (22.24%) | 311.0 V | 146.74 V (36.68%) | 138672.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 72.13 V (18.03%) | 327.9 V | 118.98 V (29.74%) | 112436.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 55.6 V (13.9%) | 344.4 V | 91.71 V (22.93%) | 86670.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 44.48 V (11.12%) | 355.5 V | 73.37 V (18.34%) | 69336.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 33.36 V (8.34%) | 366.6 V | 55.03 V (13.76%) | 52002.0 W | Drop High |
FAQ — Kabelarea för 900 Ampere vid 400 Meter (400V)
Vilken kabelarea krävs för 900A vid 400 meter (400V)?
För 900 Ampere över 400 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).
Hur stor effekt motsvarar 900A vid 400V?
Det motsvarar 623.54 kW med en rekommenderad säkring på 1000A.
Related Lengths & Currents (400V)
900A · 5m (400V)900A · 10m (400V)900A · 15m (400V)900A · 20m (400V)900A · 25m (400V)900A · 30m (400V)900A · 35m (400V)900A · 40m (400V)900A · 45m (400V)900A · 50m (400V)900A · 60m (400V)900A · 70m (400V)10A · 400m (400V)16A · 400m (400V)20A · 400m (400V)25A · 400m (400V)32A · 400m (400V)40A · 400m (400V)50A · 400m (400V)63A · 400m (400V)80A · 400m (400V)100A · 400m (400V)125A · 400m (400V)160A · 400m (400V)200A · 400m (400V)