⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 30 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 1.57%
Aluminum Wire (≤3% Drop)14 AWGDrop: 3.1V (2.59%)
Voltage at Load End118.1 VLoss: 1.88 V (18.8 W)
Power & Breaker (125%)1.2 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 30 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1.88 V (1.57%)118.1 V3.1 V (2.59%)18.8 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A1.18 V (0.99%)118.8 V1.95 V (1.63%)11.8 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A0.74 V (0.62%)119.3 V1.23 V (1.02%)7.4 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A0.47 V (0.39%)119.5 V0.77 V (0.64%)4.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.29 V (0.25%)119.7 V0.49 V (0.4%)2.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.19 V (0.15%)119.8 V0.31 V (0.25%)1.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.15 V (0.12%)119.9 V0.24 V (0.2%)1.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.12 V (0.1%)119.9 V0.19 V (0.16%)1.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.09 V (0.08%)119.9 V0.15 V (0.13%)0.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.07 V (0.06%)119.9 V0.12 V (0.1%)0.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.06 V (0.05%)119.9 V0.1 V (0.08%)0.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.05 V (0.04%)120.0 V0.08 V (0.06%)0.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.04 V (0.03%)120.0 V0.06 V (0.05%)0.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.03 V (0.03%)120.0 V0.05 V (0.04%)0.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.03 V (0.02%)120.0 V0.04 V (0.04%)0.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.02 V (0.02%)120.0 V0.04 V (0.03%)0.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.02 V (0.02%)120.0 V0.03 V (0.03%)0.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.02 V (0.01%)120.0 V0.03 V (0.02%)0.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.01 V (0.01%)120.0 V0.02 V (0.02%)0.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.01 V (0.01%)120.0 V0.02 V (0.01%)0.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.01 V (0.01%)120.0 V0.01 V (0.01%)0.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 30 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 30 feet one-way at 120V (1-Phase), you need 14 AWG copper wire. This produces a voltage drop of 1.88V (1.57%) and delivers 118.1V at the load.

What size aluminum wire is required for 10 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 14 AWG to maintain voltage drop at 3.1V (2.59%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.