⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.27%
Aluminum Wire (≤3% Drop)6 AWGDrop: 2.83V (2.36%)
Voltage at Load End117.3 VLoss: 2.73 V (27.3 W)
Power & Breaker (125%)1.2 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A10.98 V (9.15%)109.0 V18.1 V (15.09%)109.8 WDrop/Amp High
12 AWG3.31 mm²20 A6.9 V (5.75%)113.1 V11.38 V (9.48%)69.0 WDrop/Amp High
10 AWG5.26 mm²30 A4.34 V (3.62%)115.7 V7.16 V (5.97%)43.4 W~ ≤5%
8 AWG8.37 mm²50 A2.73 V (2.27%)117.3 V4.5 V (3.75%)27.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.72 V (1.43%)118.3 V2.83 V (2.36%)17.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.08 V (0.9%)118.9 V1.78 V (1.48%)10.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.86 V (0.71%)119.1 V1.41 V (1.18%)8.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.68 V (0.57%)119.3 V1.12 V (0.93%)6.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.54 V (0.45%)119.5 V0.89 V (0.74%)5.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.43 V (0.36%)119.6 V0.7 V (0.59%)4.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.34 V (0.28%)119.7 V0.56 V (0.47%)3.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.27 V (0.22%)119.7 V0.44 V (0.37%)2.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.21 V (0.18%)119.8 V0.35 V (0.29%)2.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.18 V (0.15%)119.8 V0.3 V (0.25%)1.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.15 V (0.13%)119.8 V0.25 V (0.21%)1.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.11%)119.9 V0.21 V (0.18%)1.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.11 V (0.09%)119.9 V0.19 V (0.15%)1.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.08%)119.9 V0.15 V (0.12%)0.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.06%)119.9 V0.12 V (0.1%)0.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.05%)119.9 V0.1 V (0.08%)0.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.04%)120.0 V0.07 V (0.06%)0.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 175 feet one-way at 120V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.73V (2.27%) and delivers 117.3V at the load.

What size aluminum wire is required for 10 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 2.83V (2.36%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.