🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)10 AWGDrop: 3.07V (2.56%)
Voltage at Load End117.0 VLoss: 2.96 V (29.6 W)
Power & Breaker (125%)1.2 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4.7 V (3.92%)115.3 V7.76 V (6.47%)47.0 W~ ≤5%
12 AWG3.31 mm²20 A2.96 V (2.46%)117.0 V4.88 V (4.06%)29.6 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A1.86 V (1.55%)118.1 V3.07 V (2.56%)18.6 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.17 V (0.97%)118.8 V1.93 V (1.61%)11.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.74 V (0.61%)119.3 V1.21 V (1.01%)7.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.46 V (0.39%)119.5 V0.76 V (0.64%)4.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.37 V (0.31%)119.6 V0.61 V (0.5%)3.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.29 V (0.24%)119.7 V0.48 V (0.4%)2.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.23 V (0.19%)119.8 V0.38 V (0.32%)2.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.18 V (0.15%)119.8 V0.3 V (0.25%)1.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.15 V (0.12%)119.9 V0.24 V (0.2%)1.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.12 V (0.1%)119.9 V0.19 V (0.16%)1.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.09 V (0.08%)119.9 V0.15 V (0.13%)0.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.08 V (0.06%)119.9 V0.13 V (0.11%)0.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.06 V (0.05%)119.9 V0.11 V (0.09%)0.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.06 V (0.05%)119.9 V0.09 V (0.08%)0.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.05 V (0.04%)120.0 V0.08 V (0.07%)0.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.04 V (0.03%)120.0 V0.06 V (0.05%)0.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.03%)120.0 V0.05 V (0.04%)0.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.02%)120.0 V0.04 V (0.04%)0.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.02%)120.0 V0.03 V (0.03%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 75 feet one-way at 120V (1-Phase), you need 12 AWG copper wire. This produces a voltage drop of 2.96V (2.46%) and delivers 117.0V at the load.

What size aluminum wire is required for 10 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 3.07V (2.56%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.