🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)3 AWGDrop: 6.05V (2.52%)
Voltage at Load End235.4 VLoss: 4.63 V (46.3 W)
Power & Breaker (125%)2.4 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A47.04 V (19.6%)193.0 V77.59 V (32.33%)470.4 WDrop/Amp High
12 AWG3.31 mm²20 A29.56 V (12.32%)210.4 V48.76 V (20.32%)295.6 WDrop/Amp High
10 AWG5.26 mm²30 A18.6 V (7.75%)221.4 V30.68 V (12.78%)186.0 WDrop/Amp High
8 AWG8.37 mm²50 A11.69 V (4.87%)228.3 V19.28 V (8.03%)116.9 W~ ≤5%
6 AWG13.3 mm²65 A7.36 V (3.07%)232.6 V12.13 V (5.06%)73.6 W~ ≤5%
4 AWG21.15 mm²85 A4.63 V (1.93%)235.4 V7.63 V (3.18%)46.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.67 V (1.53%)236.3 V6.05 V (2.52%)36.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.91 V (1.21%)237.1 V4.8 V (2.0%)29.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.31 V (0.96%)237.7 V3.81 V (1.59%)23.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.83 V (0.76%)238.2 V3.02 V (1.26%)18.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.45 V (0.6%)238.5 V2.39 V (1.0%)14.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.15 V (0.48%)238.8 V1.9 V (0.79%)11.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.91 V (0.38%)239.1 V1.51 V (0.63%)9.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.77 V (0.32%)239.2 V1.27 V (0.53%)7.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.64 V (0.27%)239.4 V1.06 V (0.44%)6.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.55 V (0.23%)239.4 V0.91 V (0.38%)5.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.48 V (0.2%)239.5 V0.8 V (0.33%)4.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.39 V (0.16%)239.6 V0.64 V (0.27%)3.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.32 V (0.13%)239.7 V0.53 V (0.22%)3.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.26 V (0.11%)239.7 V0.42 V (0.18%)2.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.19 V (0.08%)239.8 V0.32 V (0.13%)1.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 750 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 4.63V (1.93%) and delivers 235.4V at the load.

What size aluminum wire is required for 10 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 6.05V (2.52%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.