🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 2.87%
Aluminum Wire (≤3% Drop)10 AWGDrop: 7.16V (2.98%)
Voltage at Load End233.1 VLoss: 6.9 V (69.0 W)
Power & Breaker (125%)2.4 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A10.98 V (4.57%)229.0 V18.1 V (7.54%)109.8 W~ ≤5%
12 AWG3.31 mm²20 A6.9 V (2.87%)233.1 V11.38 V (4.74%)69.0 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A4.34 V (1.81%)235.7 V7.16 V (2.98%)43.4 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.73 V (1.14%)237.3 V4.5 V (1.87%)27.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.72 V (0.72%)238.3 V2.83 V (1.18%)17.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.08 V (0.45%)238.9 V1.78 V (0.74%)10.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.86 V (0.36%)239.1 V1.41 V (0.59%)8.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.68 V (0.28%)239.3 V1.12 V (0.47%)6.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.54 V (0.22%)239.5 V0.89 V (0.37%)5.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.43 V (0.18%)239.6 V0.7 V (0.29%)4.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.34 V (0.14%)239.7 V0.56 V (0.23%)3.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.27 V (0.11%)239.7 V0.44 V (0.18%)2.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.21 V (0.09%)239.8 V0.35 V (0.15%)2.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.18 V (0.08%)239.8 V0.3 V (0.12%)1.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.15 V (0.06%)239.8 V0.25 V (0.1%)1.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.05%)239.9 V0.21 V (0.09%)1.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.11 V (0.05%)239.9 V0.19 V (0.08%)1.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.04%)239.9 V0.15 V (0.06%)0.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.03%)239.9 V0.12 V (0.05%)0.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.03%)239.9 V0.1 V (0.04%)0.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.02%)240.0 V0.07 V (0.03%)0.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 175 feet one-way at 240V (1-Phase), you need 12 AWG copper wire. This produces a voltage drop of 6.9V (2.87%) and delivers 233.1V at the load.

What size aluminum wire is required for 10 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 7.16V (2.98%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.