🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 350 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.49V (12.39%)
Voltage at Load End11.7 VLoss: 0.3 V (30.0 W)
Power & Breaker (125%)1.2 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 350 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A219.51 V (1829.29%)0.0 V362.1 V (3017.47%)21951.5 WDrop/Amp High
12 AWG3.31 mm²20 A137.94 V (1149.52%)0.0 V227.54 V (1896.18%)13794.3 WDrop/Amp High
10 AWG5.26 mm²30 A86.8 V (723.37%)0.0 V143.19 V (1193.22%)8680.4 WDrop/Amp High
8 AWG8.37 mm²50 A54.55 V (454.59%)0.0 V89.98 V (749.86%)5455.1 WDrop/Amp High
6 AWG13.3 mm²65 A34.33 V (286.08%)0.0 V56.63 V (471.91%)3433.0 WDrop/Amp High
4 AWG21.15 mm²85 A21.59 V (179.9%)0.0 V35.61 V (296.75%)2158.8 WDrop/Amp High
3 AWG26.67 mm²100 A17.12 V (142.67%)0.0 V28.24 V (235.33%)1712.0 WDrop/Amp High
2 AWG33.62 mm²115 A13.58 V (113.17%)0.0 V22.4 V (186.68%)1358.1 WDrop/Amp High
1 AWG42.41 mm²130 A10.77 V (89.72%)1.2 V17.76 V (147.99%)1076.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.54 V (71.13%)3.5 V14.08 V (117.34%)853.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.77 V (56.43%)5.2 V11.17 V (93.08%)677.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.37 V (44.76%)6.6 V8.86 V (73.83%)537.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.26 V (35.49%)7.7 V7.03 V (58.55%)425.9 WDrop/Amp High
250 kcmil126.7 mm²255 A3.6 V (30.03%)8.4 V5.94 V (49.54%)360.4 WDrop/Amp High
300 kcmil152.0 mm²285 A3.0 V (25.03%)9.0 V4.96 V (41.29%)300.4 WDrop/Amp High
350 kcmil177.3 mm²310 A2.58 V (21.46%)9.4 V4.25 V (35.4%)257.5 WDrop/Amp High
400 kcmil202.7 mm²335 A2.25 V (18.77%)9.7 V3.72 V (30.96%)225.3 WDrop/Amp High
500 kcmil253.4 mm²380 A1.8 V (15.02%)10.2 V2.97 V (24.77%)180.2 WDrop/Amp High
600 kcmil304.0 mm²420 A1.5 V (12.52%)10.5 V2.48 V (20.65%)150.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.2 V (10.01%)10.8 V1.98 V (16.52%)120.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.9 V (7.51%)11.1 V1.49 V (12.39%)90.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 350 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 350 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.3V (2.5%) and delivers 11.7V at the load.

What size aluminum wire is required for 100 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.49V (12.39%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.