⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 350 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.35%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.86V (15.48%)
Voltage at Load End11.7 VLoss: 0.28 V (35.2 W)
Power & Breaker (125%)1.5 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 350 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A274.39 V (2286.61%)0.0 V452.62 V (3771.84%)34299.2 WDrop/Amp High
12 AWG3.31 mm²20 A172.43 V (1436.9%)0.0 V284.43 V (2370.22%)21553.5 WDrop/Amp High
10 AWG5.26 mm²30 A108.51 V (904.21%)0.0 V178.98 V (1491.53%)13563.2 WDrop/Amp High
8 AWG8.37 mm²50 A68.19 V (568.24%)0.0 V112.48 V (937.33%)8523.6 WDrop/Amp High
6 AWG13.3 mm²65 A42.91 V (357.61%)0.0 V70.79 V (589.88%)5364.1 WDrop/Amp High
4 AWG21.15 mm²85 A26.99 V (224.88%)0.0 V44.51 V (370.94%)3373.2 WDrop/Amp High
3 AWG26.67 mm²100 A21.4 V (178.33%)0.0 V35.3 V (294.17%)2675.0 WDrop/Amp High
2 AWG33.62 mm²115 A16.98 V (141.47%)0.0 V28.0 V (233.36%)2122.0 WDrop/Amp High
1 AWG42.41 mm²130 A13.46 V (112.15%)0.0 V22.2 V (184.99%)1682.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.67 V (88.92%)1.3 V17.6 V (146.67%)1333.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.46 V (70.53%)3.5 V13.96 V (116.35%)1058.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.71 V (55.95%)5.3 V11.07 V (92.29%)839.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.32 V (44.37%)6.7 V8.78 V (73.18%)665.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.5 V (37.54%)7.5 V7.43 V (61.92%)563.1 WDrop/Amp High
300 kcmil152.0 mm²285 A3.75 V (31.29%)8.2 V6.19 V (51.61%)469.4 WDrop/Amp High
350 kcmil177.3 mm²310 A3.22 V (26.83%)8.8 V5.31 V (44.25%)402.4 WDrop/Amp High
400 kcmil202.7 mm²335 A2.82 V (23.46%)9.2 V4.64 V (38.7%)352.0 WDrop/Amp High
500 kcmil253.4 mm²380 A2.25 V (18.77%)9.7 V3.72 V (30.96%)281.5 WDrop/Amp High
600 kcmil304.0 mm²420 A1.88 V (15.65%)10.1 V3.1 V (25.81%)234.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.5 V (12.52%)10.5 V2.48 V (20.65%)187.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.13 V (9.39%)10.9 V1.86 V (15.48%)140.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 350 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 350 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.28V (2.35%) and delivers 11.7V at the load.

What size aluminum wire is required for 125 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.86V (15.48%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.