⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 350 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 12.19V (2.54%)
Voltage at Load End468.2 VLoss: 11.76 V (2037.1 W)
Power & Breaker (125%)83.14 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 350 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A190.11 V (39.61%)289.9 V313.58 V (65.33%)32927.2 WDrop/Amp High
12 AWG3.31 mm²20 A119.46 V (24.89%)360.5 V197.06 V (41.05%)20691.4 WDrop/Amp High
10 AWG5.26 mm²30 A75.17 V (15.66%)404.8 V124.0 V (25.83%)13020.6 WDrop/Amp High
8 AWG8.37 mm²50 A47.24 V (9.84%)432.8 V77.93 V (16.23%)8182.6 WDrop/Amp High
6 AWG13.3 mm²65 A29.73 V (6.19%)450.3 V49.04 V (10.22%)5149.5 WDrop/Amp High
4 AWG21.15 mm²85 A18.7 V (3.89%)461.3 V30.84 V (6.42%)3238.2 WDrop/Amp High
3 AWG26.67 mm²100 A14.83 V (3.09%)465.2 V24.46 V (5.1%)2568.0 W~ ≤5%
2 AWG33.62 mm²115 A11.76 V (2.45%)468.2 V19.4 V (4.04%)2037.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A9.32 V (1.94%)470.7 V15.38 V (3.2%)1614.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A7.39 V (1.54%)472.6 V12.19 V (2.54%)1280.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A5.86 V (1.22%)474.1 V9.67 V (2.02%)1015.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.65 V (0.97%)475.3 V7.67 V (1.6%)805.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.69 V (0.77%)476.3 V6.08 V (1.27%)638.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.12 V (0.65%)476.9 V5.15 V (1.07%)540.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.6 V (0.54%)477.4 V4.29 V (0.89%)450.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.23 V (0.46%)477.8 V3.68 V (0.77%)386.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.95 V (0.41%)478.0 V3.22 V (0.67%)337.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.56 V (0.33%)478.4 V2.57 V (0.54%)270.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.3 V (0.27%)478.7 V2.15 V (0.45%)225.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.04 V (0.22%)479.0 V1.72 V (0.36%)180.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.78 V (0.16%)479.2 V1.29 V (0.27%)135.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 350 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 350 feet one-way at 480V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 11.76V (2.45%) and delivers 468.2V at the load.

What size aluminum wire is required for 100 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 12.19V (2.54%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.