🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 500 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.77%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.13V (2.55%)
Voltage at Load End233.4 VLoss: 6.64 V (1150.9 W)
Power & Breaker (125%)41.57 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A271.58 V (113.16%)0.0 V447.98 V (186.66%)47038.8 WDrop/Amp High
12 AWG3.31 mm²20 A170.66 V (71.11%)69.3 V281.51 V (117.3%)29559.2 WDrop/Amp High
10 AWG5.26 mm²30 A107.39 V (44.75%)132.6 V177.15 V (73.81%)18600.9 WDrop/Amp High
8 AWG8.37 mm²50 A67.49 V (28.12%)172.5 V111.33 V (46.39%)11689.5 WDrop/Amp High
6 AWG13.3 mm²65 A42.47 V (17.7%)197.5 V70.06 V (29.19%)7356.5 WDrop/Amp High
4 AWG21.15 mm²85 A26.71 V (11.13%)213.3 V44.06 V (18.36%)4626.0 WDrop/Amp High
3 AWG26.67 mm²100 A21.18 V (8.83%)218.8 V34.94 V (14.56%)3668.6 WDrop/Amp High
2 AWG33.62 mm²115 A16.8 V (7.0%)223.2 V27.72 V (11.55%)2910.2 WDrop/Amp High
1 AWG42.41 mm²130 A13.32 V (5.55%)226.7 V21.97 V (9.15%)2307.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.56 V (4.4%)229.4 V17.42 V (7.26%)1829.1 W~ ≤5%
2/0 AWG67.43 mm²175 A8.38 V (3.49%)231.6 V13.82 V (5.76%)1451.0 W~ ≤5%
3/0 AWG85.01 mm²200 A6.64 V (2.77%)233.4 V10.96 V (4.57%)1150.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.27 V (2.2%)234.7 V8.69 V (3.62%)912.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.46 V (1.86%)235.5 V7.35 V (3.06%)772.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.72 V (1.55%)236.3 V6.13 V (2.55%)643.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.19 V (1.33%)236.8 V5.26 V (2.19%)551.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.79 V (1.16%)237.2 V4.6 V (1.92%)482.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.23 V (0.93%)237.8 V3.68 V (1.53%)386.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.86 V (0.77%)238.1 V3.07 V (1.28%)321.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.49 V (0.62%)238.5 V2.45 V (1.02%)257.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.11 V (0.46%)238.9 V1.84 V (0.77%)193.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 500 feet one-way at 240V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 6.64V (2.77%) and delivers 233.4V at the load.

What size aluminum wire is required for 100 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.13V (2.55%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.