🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 1000 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)72× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.98%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 42.47V (353.91%)
Voltage at Load End11.6 VLoss: 0.36 V (357.6 W)
Power & Breaker (125%)12.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 1000 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6271.85 V (52265.38%)0.0 V10345.62 V (86213.46%)6271846.2 WDrop/Amp High
12 AWG3.31 mm²20 A3941.22 V (32843.5%)0.0 V6501.17 V (54176.44%)3941220.5 WDrop/Amp High
10 AWG5.26 mm²30 A2480.12 V (20667.68%)0.0 V4091.04 V (34092.02%)2480121.7 WDrop/Amp High
8 AWG8.37 mm²50 A1558.59 V (12988.29%)0.0 V2570.95 V (21424.61%)1558595.0 WDrop/Amp High
6 AWG13.3 mm²65 A980.86 V (8173.83%)0.0 V1617.96 V (13483.01%)980860.2 WDrop/Amp High
4 AWG21.15 mm²85 A616.81 V (5140.05%)0.0 V1017.44 V (8478.68%)616805.7 WDrop/Amp High
3 AWG26.67 mm²100 A489.14 V (4076.19%)0.0 V806.86 V (6723.81%)489142.9 WDrop/Amp High
2 AWG33.62 mm²115 A388.03 V (3233.55%)0.0 V640.06 V (5333.85%)388026.2 WDrop/Amp High
1 AWG42.41 mm²130 A307.6 V (2563.36%)0.0 V507.4 V (4228.34%)307602.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A243.89 V (2032.38%)0.0 V402.3 V (3352.48%)243885.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A193.47 V (1612.22%)0.0 V319.13 V (2659.41%)193466.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A153.46 V (1278.81%)0.0 V253.13 V (2109.45%)153457.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A121.69 V (1014.1%)0.0 V200.74 V (1672.8%)121692.5 WDrop/Amp High
250 kcmil126.7 mm²255 A102.96 V (858.03%)0.0 V169.84 V (1415.34%)102963.2 WDrop/Amp High
300 kcmil152.0 mm²285 A85.83 V (715.21%)0.0 V141.57 V (1179.76%)85825.3 WDrop/Amp High
350 kcmil177.3 mm²310 A73.58 V (613.15%)0.0 V121.37 V (1011.42%)73578.3 WDrop/Amp High
400 kcmil202.7 mm²335 A64.36 V (536.32%)0.0 V106.16 V (884.68%)64358.4 WDrop/Amp High
500 kcmil253.4 mm²380 A51.48 V (429.01%)0.0 V84.92 V (707.67%)51481.6 WDrop/Amp High
600 kcmil304.0 mm²420 A42.91 V (357.61%)0.0 V70.79 V (589.88%)42912.6 WDrop/Amp High
750 kcmil380.0 mm²475 A34.33 V (286.08%)0.0 V56.63 V (471.91%)34330.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A25.75 V (214.55%)0.0 V42.47 V (353.91%)25745.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 1000 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 1000 feet one-way at 12V (DC), you need 72× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.98%) and delivers 11.6V at the load.

What size aluminum wire is required for 1000 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 42.47V (353.91%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.