⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.34%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.19V (4.42%)
Voltage at Load End205.2 VLoss: 2.79 V (4827.4 W)
Power & Breaker (125%)360.27 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1357.89 V (652.83%)0.0 V2239.89 V (1076.87%)2351942.3 WDrop/Amp High
12 AWG3.31 mm²20 A853.3 V (410.24%)0.0 V1407.55 V (676.7%)1477957.7 WDrop/Amp High
10 AWG5.26 mm²30 A536.96 V (258.15%)0.0 V885.74 V (425.83%)930045.6 WDrop/Amp High
8 AWG8.37 mm²50 A337.45 V (162.23%)0.0 V556.63 V (267.61%)584473.1 WDrop/Amp High
6 AWG13.3 mm²65 A212.36 V (102.1%)0.0 V350.3 V (168.41%)367822.6 WDrop/Amp High
4 AWG21.15 mm²85 A133.54 V (64.2%)74.5 V220.28 V (105.91%)231302.1 WDrop/Amp High
3 AWG26.67 mm²100 A105.9 V (50.91%)102.1 V174.69 V (83.99%)183428.6 WDrop/Amp High
2 AWG33.62 mm²115 A84.01 V (40.39%)124.0 V138.58 V (66.62%)145509.8 WDrop/Amp High
1 AWG42.41 mm²130 A66.6 V (32.02%)141.4 V109.86 V (52.82%)115351.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A52.8 V (25.39%)155.2 V87.1 V (41.87%)91457.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.89 V (20.14%)166.1 V69.09 V (33.22%)72549.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.22 V (15.97%)174.8 V54.81 V (26.35%)57546.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.35 V (12.67%)181.7 V43.46 V (20.89%)45634.7 WDrop/Amp High
250 kcmil126.7 mm²255 A22.29 V (10.72%)185.7 V36.77 V (17.68%)38611.2 WDrop/Amp High
300 kcmil152.0 mm²285 A18.58 V (8.93%)189.4 V30.65 V (14.74%)32184.5 WDrop/Amp High
350 kcmil177.3 mm²310 A15.93 V (7.66%)192.1 V26.28 V (12.63%)27591.9 WDrop/Amp High
400 kcmil202.7 mm²335 A13.93 V (6.7%)194.1 V22.98 V (11.05%)24134.4 WDrop/Amp High
500 kcmil253.4 mm²380 A11.15 V (5.36%)196.9 V18.39 V (8.84%)19305.6 WDrop/Amp High
600 kcmil304.0 mm²420 A9.29 V (4.47%)198.7 V15.33 V (7.37%)16092.2 WDrop/Amp High
750 kcmil380.0 mm²475 A7.43 V (3.57%)200.6 V12.26 V (5.89%)12873.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.57 V (2.68%)202.4 V9.19 V (4.42%)9654.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 250 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.79V (1.34%) and delivers 205.2V at the load.

What size aluminum wire is required for 1000 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.19V (4.42%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.