🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 400 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.99V (14.16%)
Voltage at Load End116.6 VLoss: 3.43 V (3432.8 W)
Power & Breaker (125%)120.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 400 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2508.74 V (2090.62%)0.0 V4138.25 V (3448.54%)2508738.5 WDrop/Amp High
12 AWG3.31 mm²20 A1576.49 V (1313.74%)0.0 V2600.47 V (2167.06%)1576488.2 WDrop/Amp High
10 AWG5.26 mm²30 A992.05 V (826.71%)0.0 V1636.42 V (1363.68%)992048.7 WDrop/Amp High
8 AWG8.37 mm²50 A623.44 V (519.53%)0.0 V1028.38 V (856.98%)623438.0 WDrop/Amp High
6 AWG13.3 mm²65 A392.34 V (326.95%)0.0 V647.18 V (539.32%)392344.1 WDrop/Amp High
4 AWG21.15 mm²85 A246.72 V (205.6%)0.0 V406.98 V (339.15%)246722.3 WDrop/Amp High
3 AWG26.67 mm²100 A195.66 V (163.05%)0.0 V322.74 V (268.95%)195657.1 WDrop/Amp High
2 AWG33.62 mm²115 A155.21 V (129.34%)0.0 V256.02 V (213.35%)155210.5 WDrop/Amp High
1 AWG42.41 mm²130 A123.04 V (102.53%)0.0 V202.96 V (169.13%)123041.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A97.55 V (81.3%)22.4 V160.92 V (134.1%)97554.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A77.39 V (64.49%)42.6 V127.65 V (106.38%)77386.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A61.38 V (51.15%)58.6 V101.25 V (84.38%)61383.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A48.68 V (40.56%)71.3 V80.29 V (66.91%)48677.0 WDrop/Amp High
250 kcmil126.7 mm²255 A41.19 V (34.32%)78.8 V67.94 V (56.61%)41185.3 WDrop/Amp High
300 kcmil152.0 mm²285 A34.33 V (28.61%)85.7 V56.63 V (47.19%)34330.1 WDrop/Amp High
350 kcmil177.3 mm²310 A29.43 V (24.53%)90.6 V48.55 V (40.46%)29431.3 WDrop/Amp High
400 kcmil202.7 mm²335 A25.74 V (21.45%)94.3 V42.46 V (35.39%)25743.3 WDrop/Amp High
500 kcmil253.4 mm²380 A20.59 V (17.16%)99.4 V33.97 V (28.31%)20592.6 WDrop/Amp High
600 kcmil304.0 mm²420 A17.17 V (14.3%)102.8 V28.31 V (23.6%)17165.1 WDrop/Amp High
750 kcmil380.0 mm²475 A13.73 V (11.44%)106.3 V22.65 V (18.88%)13732.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.3 V (8.58%)109.7 V16.99 V (14.16%)10298.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 400 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 400 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.43V (2.86%) and delivers 116.6V at the load.

What size aluminum wire is required for 1000 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.99V (14.16%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.