⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.54%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.12V (1.77%)
Voltage at Load End119.3 VLoss: 0.65 V (643.6 W)
Power & Breaker (125%)120.0 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A313.59 V (261.33%)0.0 V517.28 V (431.07%)313592.3 WDrop/Amp High
12 AWG3.31 mm²20 A197.06 V (164.22%)0.0 V325.06 V (270.88%)197061.0 WDrop/Amp High
10 AWG5.26 mm²30 A124.01 V (103.34%)0.0 V204.55 V (170.46%)124006.1 WDrop/Amp High
8 AWG8.37 mm²50 A77.93 V (64.94%)42.1 V128.55 V (107.12%)77929.7 WDrop/Amp High
6 AWG13.3 mm²65 A49.04 V (40.87%)71.0 V80.9 V (67.42%)49043.0 WDrop/Amp High
4 AWG21.15 mm²85 A30.84 V (25.7%)89.2 V50.87 V (42.39%)30840.3 WDrop/Amp High
3 AWG26.67 mm²100 A24.46 V (20.38%)95.5 V40.34 V (33.62%)24457.1 WDrop/Amp High
2 AWG33.62 mm²115 A19.4 V (16.17%)100.6 V32.0 V (26.67%)19401.3 WDrop/Amp High
1 AWG42.41 mm²130 A15.38 V (12.82%)104.6 V25.37 V (21.14%)15380.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.19 V (10.16%)107.8 V20.11 V (16.76%)12194.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.67 V (8.06%)110.3 V15.96 V (13.3%)9673.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.67 V (6.39%)112.3 V12.66 V (10.55%)7672.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.08 V (5.07%)113.9 V10.04 V (8.36%)6084.6 WDrop/Amp High
250 kcmil126.7 mm²255 A5.15 V (4.29%)114.9 V8.49 V (7.08%)5148.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.29 V (3.58%)115.7 V7.08 V (5.9%)4291.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.68 V (3.07%)116.3 V6.07 V (5.06%)3678.9 WDrop/Amp High
400 kcmil202.7 mm²335 A3.22 V (2.68%)116.8 V5.31 V (4.42%)3217.9 WDrop/Amp High
500 kcmil253.4 mm²380 A2.57 V (2.15%)117.4 V4.25 V (3.54%)2574.1 WDrop/Amp High
600 kcmil304.0 mm²420 A2.15 V (1.79%)117.9 V3.54 V (2.95%)2145.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.72 V (1.43%)118.3 V2.83 V (2.36%)1716.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.29 V (1.07%)118.7 V2.12 V (1.77%)1287.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 50 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.65V (0.54%) and delivers 119.3V at the load.

What size aluminum wire is required for 1000 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.12V (1.77%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.