🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 60 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 1.92%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 2.39V (1.99%)
Voltage at Load End117.7 VLoss: 2.31 V (288.4 W)
Power & Breaker (125%)15.0 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 60 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A47.04 V (39.2%)73.0 V77.59 V (64.66%)5879.9 WDrop/Amp High
12 AWG3.31 mm²20 A29.56 V (24.63%)90.4 V48.76 V (40.63%)3694.9 WDrop/Amp High
10 AWG5.26 mm²30 A18.6 V (15.5%)101.4 V30.68 V (25.57%)2325.1 WDrop/Amp High
8 AWG8.37 mm²50 A11.69 V (9.74%)108.3 V19.28 V (16.07%)1461.2 WDrop/Amp High
6 AWG13.3 mm²65 A7.36 V (6.13%)112.6 V12.13 V (10.11%)919.6 WDrop/Amp High
4 AWG21.15 mm²85 A4.63 V (3.86%)115.4 V7.63 V (6.36%)578.3 WDrop/Amp High
3 AWG26.67 mm²100 A3.67 V (3.06%)116.3 V6.05 V (5.04%)458.6 WDrop/Amp High
2 AWG33.62 mm²115 A2.91 V (2.43%)117.1 V4.8 V (4.0%)363.8 WDrop/Amp High
1 AWG42.41 mm²130 A2.31 V (1.92%)117.7 V3.81 V (3.17%)288.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.83 V (1.52%)118.2 V3.02 V (2.51%)228.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.45 V (1.21%)118.5 V2.39 V (1.99%)181.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.15 V (0.96%)118.8 V1.9 V (1.58%)143.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.91 V (0.76%)119.1 V1.51 V (1.25%)114.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.77 V (0.64%)119.2 V1.27 V (1.06%)96.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.64 V (0.54%)119.4 V1.06 V (0.88%)80.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.55 V (0.46%)119.4 V0.91 V (0.76%)69.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.48 V (0.4%)119.5 V0.8 V (0.66%)60.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.39 V (0.32%)119.6 V0.64 V (0.53%)48.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.32 V (0.27%)119.7 V0.53 V (0.44%)40.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.26 V (0.21%)119.7 V0.42 V (0.35%)32.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.19 V (0.16%)119.8 V0.32 V (0.27%)24.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 60 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 60 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 2.31V (1.92%) and delivers 117.7V at the load.

What size aluminum wire is required for 125 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 2.39V (1.99%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.