⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)8 AWGDrop: 5.01V (2.09%)
Voltage at Load End235.2 VLoss: 4.83 V (125.6 W)
Power & Breaker (125%)6.24 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A12.22 V (5.09%)227.8 V20.16 V (8.4%)317.5 WDrop/Amp High
12 AWG3.31 mm²20 A7.68 V (3.2%)232.3 V12.67 V (5.28%)199.5 W~ ≤5%
10 AWG5.26 mm²30 A4.83 V (2.01%)235.2 V7.97 V (3.32%)125.6 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A3.04 V (1.27%)237.0 V5.01 V (2.09%)78.9 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.91 V (0.8%)238.1 V3.15 V (1.31%)49.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.2 V (0.5%)238.8 V1.98 V (0.83%)31.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.95 V (0.4%)239.0 V1.57 V (0.66%)24.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.76 V (0.32%)239.2 V1.25 V (0.52%)19.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.6 V (0.25%)239.4 V0.99 V (0.41%)15.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.48 V (0.2%)239.5 V0.78 V (0.33%)12.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.38 V (0.16%)239.6 V0.62 V (0.26%)9.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.3 V (0.12%)239.7 V0.49 V (0.21%)7.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.24 V (0.1%)239.8 V0.39 V (0.16%)6.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.2 V (0.08%)239.8 V0.33 V (0.14%)5.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.17 V (0.07%)239.8 V0.28 V (0.11%)4.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.14 V (0.06%)239.9 V0.24 V (0.1%)3.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.13 V (0.05%)239.9 V0.21 V (0.09%)3.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.1 V (0.04%)239.9 V0.17 V (0.07%)2.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.03%)239.9 V0.14 V (0.06%)2.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.03%)239.9 V0.11 V (0.05%)1.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.02%)239.9 V0.08 V (0.03%)1.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 150 feet one-way at 240V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 4.83V (2.01%) and delivers 235.2V at the load.

What size aluminum wire is required for 15 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 5.01V (2.09%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.