⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

200 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 200 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 1.66%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 4.41V (1.84%)
Voltage at Load End236.0 VLoss: 3.99 V (1381.1 W)
Power & Breaker (125%)83.14 kW250A Breaker Recommended

All AWG & kcmil Wire Gauges for 200 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A162.95 V (67.89%)77.1 V268.79 V (111.99%)56446.6 WDrop/Amp High
12 AWG3.31 mm²20 A102.4 V (42.66%)137.6 V168.91 V (70.38%)35471.0 WDrop/Amp High
10 AWG5.26 mm²30 A64.44 V (26.85%)175.6 V106.29 V (44.29%)22321.1 WDrop/Amp High
8 AWG8.37 mm²50 A40.49 V (16.87%)199.5 V66.8 V (27.83%)14027.4 WDrop/Amp High
6 AWG13.3 mm²65 A25.48 V (10.62%)214.5 V42.04 V (17.51%)8827.7 WDrop/Amp High
4 AWG21.15 mm²85 A16.03 V (6.68%)224.0 V26.43 V (11.01%)5551.3 WDrop/Amp High
3 AWG26.67 mm²100 A12.71 V (5.3%)227.3 V20.96 V (8.73%)4402.3 WDrop/Amp High
2 AWG33.62 mm²115 A10.08 V (4.2%)229.9 V16.63 V (6.93%)3492.2 WDrop/Amp High
1 AWG42.41 mm²130 A7.99 V (3.33%)232.0 V13.18 V (5.49%)2768.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.34 V (2.64%)233.7 V10.45 V (4.35%)2195.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.03 V (2.09%)235.0 V8.29 V (3.45%)1741.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.99 V (1.66%)236.0 V6.58 V (2.74%)1381.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.16 V (1.32%)236.8 V5.22 V (2.17%)1095.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.68 V (1.11%)237.3 V4.41 V (1.84%)926.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.23 V (0.93%)237.8 V3.68 V (1.53%)772.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.91 V (0.8%)238.1 V3.15 V (1.31%)662.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.67 V (0.7%)238.3 V2.76 V (1.15%)579.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.34 V (0.56%)238.7 V2.21 V (0.92%)463.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.11 V (0.46%)238.9 V1.84 V (0.77%)386.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.89 V (0.37%)239.1 V1.47 V (0.61%)309.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.67 V (0.28%)239.3 V1.1 V (0.46%)231.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 200 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 200A load over 150 feet one-way at 240V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 3.99V (1.66%) and delivers 236.0V at the load.

What size aluminum wire is required for 200 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 4.41V (1.84%).

What breaker size is needed for a 200A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (200A × 1.25 = 250.0A), which corresponds to a standard 250A circuit breaker.