⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)12 AWGDrop: 6.33V (2.64%)
Voltage at Load End233.9 VLoss: 6.11 V (158.8 W)
Power & Breaker (125%)6.24 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6.11 V (2.55%)233.9 V10.08 V (4.2%)158.8 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A3.84 V (1.6%)236.2 V6.33 V (2.64%)99.8 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A2.42 V (1.01%)237.6 V3.99 V (1.66%)62.8 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.52 V (0.63%)238.5 V2.5 V (1.04%)39.5 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.96 V (0.4%)239.0 V1.58 V (0.66%)24.8 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.6 V (0.25%)239.4 V0.99 V (0.41%)15.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.48 V (0.2%)239.5 V0.79 V (0.33%)12.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.38 V (0.16%)239.6 V0.62 V (0.26%)9.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.3 V (0.12%)239.7 V0.49 V (0.21%)7.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.24 V (0.1%)239.8 V0.39 V (0.16%)6.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.19 V (0.08%)239.8 V0.31 V (0.13%)4.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.15 V (0.06%)239.9 V0.25 V (0.1%)3.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.12 V (0.05%)239.9 V0.2 V (0.08%)3.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.1 V (0.04%)239.9 V0.17 V (0.07%)2.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.08 V (0.03%)239.9 V0.14 V (0.06%)2.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.07 V (0.03%)239.9 V0.12 V (0.05%)1.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.06 V (0.03%)239.9 V0.1 V (0.04%)1.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.02%)239.9 V0.08 V (0.03%)1.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.04 V (0.02%)240.0 V0.07 V (0.03%)1.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.01%)240.0 V0.06 V (0.02%)0.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)240.0 V0.04 V (0.02%)0.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 75 feet one-way at 240V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 6.11V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 15 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 12 AWG to maintain voltage drop at 6.33V (2.64%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.