⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.19%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.46V (2.28%)
Voltage at Load End234.7 VLoss: 5.26 V (78.9 W)
Power & Breaker (125%)3.6 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A21.17 V (8.82%)218.8 V34.92 V (14.55%)317.5 WDrop/Amp High
12 AWG3.31 mm²20 A13.3 V (5.54%)226.7 V21.94 V (9.14%)199.5 WDrop/Amp High
10 AWG5.26 mm²30 A8.37 V (3.49%)231.6 V13.81 V (5.75%)125.6 W~ ≤5%
8 AWG8.37 mm²50 A5.26 V (2.19%)234.7 V8.68 V (3.62%)78.9 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.31 V (1.38%)236.7 V5.46 V (2.28%)49.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.08 V (0.87%)237.9 V3.43 V (1.43%)31.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.65 V (0.69%)238.3 V2.72 V (1.13%)24.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.31 V (0.55%)238.7 V2.16 V (0.9%)19.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.04 V (0.43%)239.0 V1.71 V (0.71%)15.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.82 V (0.34%)239.2 V1.36 V (0.57%)12.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.65 V (0.27%)239.3 V1.08 V (0.45%)9.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.52 V (0.22%)239.5 V0.85 V (0.36%)7.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.41 V (0.17%)239.6 V0.68 V (0.28%)6.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.35 V (0.14%)239.7 V0.57 V (0.24%)5.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.29 V (0.12%)239.7 V0.48 V (0.2%)4.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.25 V (0.1%)239.8 V0.41 V (0.17%)3.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.22 V (0.09%)239.8 V0.36 V (0.15%)3.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.17 V (0.07%)239.8 V0.29 V (0.12%)2.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.06%)239.9 V0.24 V (0.1%)2.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.05%)239.9 V0.19 V (0.08%)1.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.04%)239.9 V0.14 V (0.06%)1.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 225 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.26V (2.19%) and delivers 234.7V at the load.

What size aluminum wire is required for 15 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.46V (2.28%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.