⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 1.94%
Aluminum Wire (≤3% Drop)8 AWGDrop: 4.82V (2.01%)
Voltage at Load End235.3 VLoss: 4.65 V (69.8 W)
Power & Breaker (125%)3.6 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A11.76 V (4.9%)228.2 V19.4 V (8.08%)176.4 W~ ≤5%
12 AWG3.31 mm²20 A7.39 V (3.08%)232.6 V12.19 V (5.08%)110.8 W~ ≤5%
10 AWG5.26 mm²30 A4.65 V (1.94%)235.3 V7.67 V (3.2%)69.8 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.92 V (1.22%)237.1 V4.82 V (2.01%)43.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.84 V (0.77%)238.2 V3.03 V (1.26%)27.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.16 V (0.48%)238.8 V1.91 V (0.79%)17.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.92 V (0.38%)239.1 V1.51 V (0.63%)13.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.73 V (0.3%)239.3 V1.2 V (0.5%)10.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.58 V (0.24%)239.4 V0.95 V (0.4%)8.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.46 V (0.19%)239.5 V0.75 V (0.31%)6.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.36 V (0.15%)239.6 V0.6 V (0.25%)5.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.29 V (0.12%)239.7 V0.47 V (0.2%)4.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.23 V (0.1%)239.8 V0.38 V (0.16%)3.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.19 V (0.08%)239.8 V0.32 V (0.13%)2.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.16 V (0.07%)239.8 V0.27 V (0.11%)2.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.14 V (0.06%)239.9 V0.23 V (0.09%)2.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.12 V (0.05%)239.9 V0.2 V (0.08%)1.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.1 V (0.04%)239.9 V0.16 V (0.07%)1.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.03%)239.9 V0.13 V (0.06%)1.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.03%)239.9 V0.11 V (0.04%)1.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.02%)240.0 V0.08 V (0.03%)0.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 125 feet one-way at 240V (1-Phase), you need 10 AWG copper wire. This produces a voltage drop of 4.65V (1.94%) and delivers 235.3V at the load.

What size aluminum wire is required for 15 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 4.82V (2.01%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.