🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.31%
Aluminum Wire (≤3% Drop)2 AWGDrop: 5.76V (2.4%)
Voltage at Load End234.4 VLoss: 5.55 V (222.1 W)
Power & Breaker (125%)9.6 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A56.45 V (23.52%)183.6 V93.11 V (38.8%)2257.9 WDrop/Amp High
12 AWG3.31 mm²20 A35.47 V (14.78%)204.5 V58.51 V (24.38%)1418.8 WDrop/Amp High
10 AWG5.26 mm²30 A22.32 V (9.3%)217.7 V36.82 V (15.34%)892.8 WDrop/Amp High
8 AWG8.37 mm²50 A14.03 V (5.84%)226.0 V23.14 V (9.64%)561.1 WDrop/Amp High
6 AWG13.3 mm²65 A8.83 V (3.68%)231.2 V14.56 V (6.07%)353.1 W~ ≤5%
4 AWG21.15 mm²85 A5.55 V (2.31%)234.4 V9.16 V (3.82%)222.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.4 V (1.83%)235.6 V7.26 V (3.03%)176.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.49 V (1.46%)236.5 V5.76 V (2.4%)139.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.77 V (1.15%)237.2 V4.57 V (1.9%)110.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.19 V (0.91%)237.8 V3.62 V (1.51%)87.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.74 V (0.73%)238.3 V2.87 V (1.2%)69.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.38 V (0.58%)238.6 V2.28 V (0.95%)55.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.1 V (0.46%)238.9 V1.81 V (0.75%)43.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.93 V (0.39%)239.1 V1.53 V (0.64%)37.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.77 V (0.32%)239.2 V1.27 V (0.53%)30.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.66 V (0.28%)239.3 V1.09 V (0.46%)26.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.58 V (0.24%)239.4 V0.96 V (0.4%)23.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.46 V (0.19%)239.5 V0.76 V (0.32%)18.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.39 V (0.16%)239.6 V0.64 V (0.27%)15.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.31 V (0.13%)239.7 V0.51 V (0.21%)12.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.1%)239.8 V0.38 V (0.16%)9.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 225 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.55V (2.31%) and delivers 234.4V at the load.

What size aluminum wire is required for 40 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 5.76V (2.4%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.