🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 0.35V (2.92%)
Voltage at Load End11.6 VLoss: 0.35 V (5.3 W)
Power & Breaker (125%)0.18 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A25.87 V (215.59%)0.0 V42.68 V (355.63%)388.1 WDrop/Amp High
12 AWG3.31 mm²20 A16.26 V (135.48%)0.0 V26.82 V (223.48%)243.9 WDrop/Amp High
10 AWG5.26 mm²30 A10.23 V (85.25%)1.8 V16.88 V (140.63%)153.5 WDrop/Amp High
8 AWG8.37 mm²50 A6.43 V (53.58%)5.6 V10.61 V (88.38%)96.4 WDrop/Amp High
6 AWG13.3 mm²65 A4.05 V (33.72%)8.0 V6.67 V (55.62%)60.7 WDrop/Amp High
4 AWG21.15 mm²85 A2.54 V (21.2%)9.5 V4.2 V (34.97%)38.2 WDrop/Amp High
3 AWG26.67 mm²100 A2.02 V (16.81%)10.0 V3.33 V (27.74%)30.3 WDrop/Amp High
2 AWG33.62 mm²115 A1.6 V (13.34%)10.4 V2.64 V (22.0%)24.0 WDrop/Amp High
1 AWG42.41 mm²130 A1.27 V (10.57%)10.7 V2.09 V (17.44%)19.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.01 V (8.38%)11.0 V1.66 V (13.83%)15.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.8 V (6.65%)11.2 V1.32 V (10.97%)12.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.63 V (5.28%)11.4 V1.04 V (8.7%)9.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.5 V (4.18%)11.5 V0.83 V (6.9%)7.5 W~ ≤5%
250 kcmil126.7 mm²255 A0.42 V (3.54%)11.6 V0.7 V (5.84%)6.4 W~ ≤5%
300 kcmil152.0 mm²285 A0.35 V (2.95%)11.6 V0.58 V (4.87%)5.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.3 V (2.53%)11.7 V0.5 V (4.17%)4.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.27 V (2.21%)11.7 V0.44 V (3.65%)4.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.21 V (1.77%)11.8 V0.35 V (2.92%)3.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.18 V (1.48%)11.8 V0.29 V (2.43%)2.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.14 V (1.18%)11.9 V0.23 V (1.95%)2.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.89%)11.9 V0.18 V (1.46%)1.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 275 feet one-way at 12V (DC), you need 300 kcmil copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.6V at the load.

What size aluminum wire is required for 15 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 0.35V (2.92%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.